Plan Review Notes
Plan Review Notes For Permit 14040608
Permit Number 14040608
Review Stop B
Sequence Number 2
Notes
Date Text
2014-06-24 07:36:092010 FBC
  
 DENIED BY BUILDING
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS REVIEW HAVE
 NOT BEEN ADDRESSED :
  
 2) SUBMIT ENERGY CALCULATIONS FOR THE NEW ROOM. 2010
 FBC ENERGY SECTION 401.2
  
 3) SPECIFY THE WALL AND CEILING INSULATION ON THE
 PLANS. CITY AMENDMENTS 107.2.1 AND 2010 FBC ENERGY
 SECTION 401.2
  
 4) THE STUCCO ON THE WALL IS REQUIRED TO BE 7/8" THICK
 PER ASTM C 926.
  
 5) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE EXTERIOR STUCCO AND THE
 WATER-RESISTIVE BARRIER REQUIRED BY FBCR 703.1.1.
  
 6) SPECIFY THE SOFFIT COVERING MATERIAL THAT WILL BE
 USED. CITY AMENDMENTS 107.2.1
  
 7) SHOW COMPLIANCE WITH FBCR 806.1 FOR ROOF
 VENTILATION.
  
 8) SPECIFY THE CEILING COVERING MATERIAL ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  
 10) SUBMIT PRODUCT APPROVALS FOR THE NEW EXTERIOR DOOR
 AND WINDOWS THAT ARE SHOWN ON THE PLANS AS REQUIRED BY
 DCA RULE 9N-3.
  
 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 WHICH REQUIRES
 LARGE MISSILE IMPACT PROTECTION FOR GLAZED OPENINGS. (
 NEW COMMENT. THE REVISED PLANS SPECIFY HURRICANE
 SHUTTERS. SUBMIT TWO COPIES OF THE PRODUCT APPROVALS
 AND AN INSTALLATION SCHEDULE WITH A KEY PLAN. )
  
 13) THE VALUE OF WORK SPECIFIED ON THE APPLICATION OF
 $2500.00 IS LOW. THE VALUE IS TO BE THE COSTS OF ALL
 MATERIALS, LABOR, DESIGN COSTS, OVERHEAD AND PROFIT
 (THE TOTAL REPLACEMENT VALUE FOR THE WORK BEING DONE IS
 TO BE USED). CITY AMENDMENTS 109.3
  
 14) IN ORDER TO HELP SPEED THE NEXT REVIEW, PLEASE
 SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.
  