Plan Review Notes
Plan Review Notes For Permit 14040535
Permit Number 14040535
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-21 11:31:4014040535
 854 CONNISTON RD.
 CHURCH REMODEL REVISION TO MASTER PERMIT #12090675)
  
 THE FOLLOWING NOTES WERE PLACED ON THE PLAN.
  
 PROVIDE SAFETY LABELING FOR FLASH PROTECTION. NEC
 110.22, 110.16
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCI PROTECTION. NEC 422.52
 PROVIDE AN ENGINEERING DETAIL FOR THE LIGHT POLES AND
 FIXTURES WHICH INDICATES CAPABILITY TO WITH STAND HIGH
 WIND. PROVIDE AN EXPOSURE CATEGORY AND IMPORTANCE
 FACTOR FOR THE DESIGN. FBC 1609, ASCE 7-10
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR LOW VOLTAGE
 SYSTEMS, FIRE ALARM SYSTEMS AND SITE LIGHTING.
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-373-3701
  