| Plan Review Notes For Permit 14040535 |
| Permit Number |
14040535 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-21 11:31:40 | 14040535 | | | 854 CONNISTON RD. | | | CHURCH REMODEL REVISION TO MASTER PERMIT #12090675) | | | | | | THE FOLLOWING NOTES WERE PLACED ON THE PLAN. | | | | | | PROVIDE SAFETY LABELING FOR FLASH PROTECTION. NEC | | | 110.22, 110.16 | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GFCI PROTECTION. NEC 422.52 | | | PROVIDE AN ENGINEERING DETAIL FOR THE LIGHT POLES AND | | | FIXTURES WHICH INDICATES CAPABILITY TO WITH STAND HIGH | | | WIND. PROVIDE AN EXPOSURE CATEGORY AND IMPORTANCE | | | FACTOR FOR THE DESIGN. FBC 1609, ASCE 7-10 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR LOW VOLTAGE | | | SYSTEMS, FIRE ALARM SYSTEMS AND SITE LIGHTING. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | |
|