2014-04-16 16:28:07ELECTRIC DENIED. FBC 107.2.1. AND FBC 107.3.5.1.2
 ELECTRICAL. PROVIDE PANEL SCHEDULES INDICATING THE
 OVERCURRENT DEVICES FOR THE NEW AND EXISTING LOADS.
 IDENTIFY THE CIRCUITRY IN THE EXISTING CONDUITS. SHOW
 THE NEW CONDUITS FROM THE NEW BOAT LIFT CONTROL PANEL
 AND INDICATE THE LOADS THAT ARE CONTROLED AND HOW THEY
 ARE BEING FED.
  
 FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN
 REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS
 EXAMINER, PX3421 WITH THE CITY OF WEST PALM BEACH. I
 CAN BE AT 561-805-6717 OR AT [email protected]