| 2014-04-29 16:43:36 | BUILDING PLAN REVIEW |
| | PERMIT: 14040504 |
| | ADD: 207 CLEMATIS ST. |
| | CONT: GEORGE FRAKER |
| | TEL: (561)502-4699 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY APRIL 29/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET # 1 THE FRONT ELEVATION SHOWS THE USE OF A |
| | 22'-0" LONG HORIZONTAL MULLION. THE PRODUCT APPROVAL |
| | SUBMITTED NOA 11-0922.01 |
| | LONGEST SPAN OF 13.33 FT OR 160 INCHES. PLEASE PROVIDE |
| | A STRUCTURAL ELEMENT THAT WILL BE ABLE TO CARRY THE |
| | LOADS FOR THE 22'-0" SPAN. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING, |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS, MULLIONS |
| | |
| | 2) SHEET # 1 INDICATES IN THE NOTES THE INSTALATION OF |
| | EUROWALL FOLDING DOOR SYSTEM, NO PRODUCT APPROVAL WAS |
| | SUBMITTED FOR THIS REVIEW. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING, |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 3) SHEET # 1 APPEARS TO BE A OUTSWING DOOR SYSTEM, |
| | PLEASE PROVIDE WHERE THE PROPERTY LINE IS LOCATED SHOW |
| | COMPLIANCE WITH : |
| | 2010 FBC-B 202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 |
| | FEET IN HEIGHT. |
| | ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| | AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| | PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| | THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 4) NOTE MOST OUTSWING DOOR SYSTEMS ARE NOT PART OF A |
| | EGRESS SYSTEM, SINCE WHEN THE DOOR SYSTEM IS CLOSED THE |
| | ENTRY DOOR IS A SWING DOOR, BUT THERE IS USUALLY A |
| | BOTTOM TRACK, PLEASE PROVIDE DETAILS THAT WILL COMPLY |
| | WITH 2010 FL ACCESSIBILITY CODE: |
| | MANEUVERING CLEARANCES AT RECESSED DOORS AND GATES |
| | 404.2.4.4 FLOOR OR GROUND SURFACE. FLOOR OR GROUND |
| | SURFACE WITHIN REQUIRED MANEUVERING CLEARANCES SHALL |
| | COMPLY WITH 302. CHANGES IN LEVEL ARE NOT PERMITTED. |
| | EXCEPTIONS: |
| | 1. SLOPES NOT STEEPER THAN 1:48 SHALL BE PERMITTED. |
| | 2. CHANGES IN LEVEL AT THRESHOLDS COMPLYING WITH |
| | 404.2.5 SHALL BE PERMITTED. |
| | 404.2.5 THRESHOLDS. |
| | THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| | (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| | LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| | |
| | 5) SHEET # 1 ALSO HAS A DETAIL OF NEW ACOUSTICAL |
| | CEILING SYSTEM. THE PLANS INDICATE SEE MANUFACTURERS |
| | INSTRUCTIONS FOR DETAILS. NO LITERATURE HAS BEEN |
| | SUVMITTED. PLEASE PROVIDE CODE COMPLIANCE WITH 2010 |
| | FBC-B: |
| | 808.1 ACOUSTICAL CEILING SYSTEMS. |
| | THE QUALITY, DESIGN, FABRICATION AND ERECTION OF METAL |
| | SUSPENSION SYSTEMS FOR ACOUSTICAL TILE AND LAY-IN PANEL |
| | CEILINGS IN BUILDINGS OR STRUCTURES SHALL CONFORM WITH |
| | GENERALLY ACCEPTED ENGINEERING PRACTICE, THE PROVISIONS |
| | OF THIS CHAPTER AND OTHER APPLICABLE REQUIREMENTS OF |
| | THIS CODE. |
| | |
| | 808.1.1 MATERIALS AND INSTALLATION. |
| | ACOUSTICAL MATERIALS COMPLYING WITH THE INTERIOR FINISH |
| | REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS AND |
| | APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH. |
| | |
| | 808.1.1.1 SUSPENDED ACOUSTICAL CEILINGS. |
| | SUSPENDED ACOUSTICAL CEILING SYSTEMS SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND |
| | ASTM C 636. |
| | |
| | : WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |