| 2014-05-02 18:00:22 | BUILDING PLAN REVIEW |
| | PERMIT: 14040502 |
| | ADD: 3114 TUXEDO AVE. |
| | CONT: TBD |
| | TEL: (561)799-3700 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MAY 02/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE CHANGE OF |
| | OCCUPANCY, IT IS MORE A CHANGE OF USE AND MATERIALS. |
| | THE HANDLING OF THEM AND STORING THEM AS WELL. |
| | |
| | THE TYPES OF MATERIALS THAT YOUR FIRM WILL BE STORING |
| | AND PROCESSING IS VARIOUS METALS. FORKLIFTS WILL BE |
| | USED IN MOVING TTHE METALS AROUND THE SITE. WHAT TYPE |
| | OF FUEL DOES THE FORK LIFTS USE? IF GASOLINE WHAT TPE |
| | OF STORAGE CONTAINMENT IS USED TO CREATE CONTROL AREA. |
| | 2010 FBC-B TABLE 307.1(2) |
| | MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF |
| | HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD |
| | WILL ALLOW 30 GALLONS OF GASOLINE TO BE STORED IN |
| | APPROVED CONTAINERS AND NOT BE CONSIDERED A HAZORDOUS |
| | OCCUPANCY. |
| | FOOTNOTE (B) .THE AGGREGATE QUANTITY IN USE AND STORAGE |
| | SHALL NOT EXCEED THE QUANTITY LISTED FOR STORAGE |
| | FOOTNOTE (P.) THE FOLLOWING SHALL NOT BE INCLUDED IN |
| | DETERMINING THE MAXIMUM ALLOWABLE QUANTITIES: |
| | 1. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON VEHICLES. |
| | 2. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON MOTORIZED |
| | EQUIPMENT OPERATED IN ACCORDANCE WITH THIS CODE. |
| | 3. GASEOUS FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES |
| | REGULATED BY THE FLORIDA BUILDING CODE, FUEL GAS. |
| | 4. LIQUID FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES |
| | REGULATED BY THE FLORIDA BUILDING CODE, MECHANICAL. |
| | FOOTNOTE (M) FOR GALLONS OF LIQUIDS, DIVIDE THE AMOUNT |
| | IN POUNDS BY 10 IN ACCORDANCE WITH THE FLORIDA FIRE |
| | PREVENTION CODE |
| | FOOTNOTE (F) . MAXIMUM ALLOWABLE QUANTITIES SHALL BE |
| | INCREASED 100 PERCENT WHEN STORED IN APPROVED STORAGE |
| | CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES AS |
| | SPECIFIED IN THE FLORIDA FIRE PREVENTION CODE. WHERE |
| | NOTE E ALSO APPLIES, THE INCREASE FOR BOTH NOTES SHALL |
| | BE APPLIED ACCUMULATIVELY. |
| | |
| | 2) WILL THERE BE CUTTING OF ALLUMINUM AND MAGNESIUM? |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |