| Plan Review Notes For Permit 14040472 |
| Permit Number |
14040472 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-17 07:36:06 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE POOL PLANS ARE REQUIRED TO BE SIGNED AND SEALED | | | BY THE FLORIDA LICENSED ENGINEER RESPONSIBLE FOR THE | | | DESIGN. FS 471 AND CITY AMENDMENTS 107.2.1 | | | | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS INCLUDING THE PUMP CURVE FOR THE 2.5 HP | | | SWIMMING POOL PUMP THAT WILL BE INSTALLED. CITY | | | AMENDMENTS 107.2.1.3 | | | | | | 3) SHOW COMPLIANCE WITH ANSI/APSP-7 2006 SECTION 4.4 | | | WHICH LIMITS WATER VELOCITY TO A MAXIMUM OF 6 FT/SEC IN | | | THE BRANCH SUCTION PIPING WHEN ONE OF A PAIR IS | | | BLOCKED. | | | | | | 4) SUBMIT TWO SETS OF TDH CALCULATIONS, WATER VELOCITY | | | CALCULATIONS AND TURNOVER RATE CALCULATIONS. CITY | | | AMENDMENTS 107.2.1.3, FBC R4101.6.3 AND R4101.20 | | | | | | 5) SHOW THAT THE SUCTION OUTLET COVERS ARE LISTED IN | | | ACCORDANCE WITH ANSI/ASME A112.19.8. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|