2014-04-17 07:36:062010 FBC
  
 DENIED BY PLUMBING
  
 1) THE POOL PLANS ARE REQUIRED TO BE SIGNED AND SEALED
 BY THE FLORIDA LICENSED ENGINEER RESPONSIBLE FOR THE
 DESIGN. FS 471 AND CITY AMENDMENTS 107.2.1
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS INCLUDING THE PUMP CURVE FOR THE 2.5 HP
 SWIMMING POOL PUMP THAT WILL BE INSTALLED. CITY
 AMENDMENTS 107.2.1.3
  
 3) SHOW COMPLIANCE WITH ANSI/APSP-7 2006 SECTION 4.4
 WHICH LIMITS WATER VELOCITY TO A MAXIMUM OF 6 FT/SEC IN
 THE BRANCH SUCTION PIPING WHEN ONE OF A PAIR IS
 BLOCKED.
  
 4) SUBMIT TWO SETS OF TDH CALCULATIONS, WATER VELOCITY
 CALCULATIONS AND TURNOVER RATE CALCULATIONS. CITY
 AMENDMENTS 107.2.1.3, FBC R4101.6.3 AND R4101.20
  
 5) SHOW THAT THE SUCTION OUTLET COVERS ARE LISTED IN
 ACCORDANCE WITH ANSI/ASME A112.19.8.
  