| 2014-05-28 17:49:08 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- ROOF BUILT UP: |
| | PROVIDE SIGNED AND SEALED STRUCTURAL EVALUATION BY |
| | DESIGN PROFESSIONAL AS REQUIRED BY SEC. 506.2.2.1 OF |
| | 2010 FBC-EXISTING BUILDING. DESIGN PROFESSIONAL TO |
| | PROVIDE STRUCTURAL ANALYSIS SHOWING THAT PROPOSED |
| | STRUCTURAL MEMBERS AND CONNECTORS SPECIFIED ON PLANS |
| | SUBMITTED WILL MEET THE LATERAL AND UPLIFT LOADS |
| | REQUIRED BY SEC. R301 OF 2010 FBC. |
| | |
| | 3- DESIGN PROFESSIONAL TO REVISE INFORMATION ON SHEET |
| | 6.0 |
| | A) REVISE THE ROOF ZONES ON THE GABLE ROOF PLAN. THE |
| | WHOLE GABLE END FOR A MINIMUM DISTANCE OF 5'-0" IS |
| | CONSIDERED ROOF ZONE #3. SEE FIGURE R803.2.3.1 OF 2010 |
| | FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| | |
| | B) REVISE THE DESIGN CRITERIA: CURRENT ASCE EDITION |
| | THAT CORRESPONDS TO FBC 2010 IS ASCE 7-10 NOT ASCE |
| | 7-05. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| | PROFIT AND DESIGN PROFESSIONAL FEES. UPDATE THE |
| | VALUATION AS REQUIRED TO INCLUDE THE ROOF BUILT UP, |
| | REPLACEMENT OF DOOR AND WINDOWS, DESIGN PROFESSIONAL |
| | FEES. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. (NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR). |
| | |
| | B) EXTERIOR DOORS. PROVIDE THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED |
| | FROM JELD WEN. DRAWINGS SUBMITTED DON'T HAVE ANY |
| | REFERENCE TO THE APPROVED FLORIDA PRODUCT APPROVAL. |
| | UNABLE TO VERIFY IF IT WAS APPROVED OR NOT. |
| | |
| | 6- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED: |
| | A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM |
| | WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING |
| | BUILDING. |
| | |
| | B) SHEET 4.0: CURRENT ASCE EDITION THAT CORRESPONDS TO |
| | FBC-2010 IS ASCE 7-10 NOT ASCE 7-05. REVISE AS |
| | REQUIRED. |
| | |
| | *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |