| Plan Review Notes For Permit 14040448 |
| Permit Number |
14040448 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-05-27 15:26:36 | ELECTRICAL PROVISO FOR PERMIT 14040448 | | | 1. AS PER NEC 210.8(B), ALL 125 V. SINGLE PHASE 15 & 20 | | | AMP RECEPTACLES INSTALLED IN KITCHENS SHALL BE GFCI | | | PROTECTION, (THIS MEANS EVERY OUTLET IN THE FOOD PREP | | | AREA). | | | 2. AS PER NEC 600.5(A), THERE SHALL BE AN ACCESSIBLE | | | OUTLET FOR SIGN AT EACH ENTRANCE. (THIS MEANS BOTH | | | DOORS) | | | 3. UNLESS INSTALLED & COMPLETED BY THE ELECTRICAL | | | CONTRACTOR OF RECORD, A SEPARATE PERMIT SHALL BE | | | SECURED FOR ANY LOW VOLTAGE, DATA AND/OR COMMUNICATION | | | SYSTEMS. | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | | | | |
|