Plan Review Notes
Plan Review Notes For Permit 14040448
Permit Number 14040448
Review Stop E
Sequence Number 2
Notes
Date Text
2014-05-27 15:26:36ELECTRICAL PROVISO FOR PERMIT 14040448
 1. AS PER NEC 210.8(B), ALL 125 V. SINGLE PHASE 15 & 20
 AMP RECEPTACLES INSTALLED IN KITCHENS SHALL BE GFCI
 PROTECTION, (THIS MEANS EVERY OUTLET IN THE FOOD PREP
 AREA).
 2. AS PER NEC 600.5(A), THERE SHALL BE AN ACCESSIBLE
 OUTLET FOR SIGN AT EACH ENTRANCE. (THIS MEANS BOTH
 DOORS)
 3. UNLESS INSTALLED & COMPLETED BY THE ELECTRICAL
 CONTRACTOR OF RECORD, A SEPARATE PERMIT SHALL BE
 SECURED FOR ANY LOW VOLTAGE, DATA AND/OR COMMUNICATION
 SYSTEMS.
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.