| 2014-04-17 07:18:59 | PLUMBING PLAN REVIEW |
| | PERMIT: 14040448 |
| | ADD: 205 CLEMATIS ST |
| | CONT: BLUEWATER BUILDER |
| | TEL: (561)312-8477 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. APRIL 17/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A DETAIL OF THE GREASE INTERCEPTOR, |
| | REQUIRED SERVICE SINK, WASTE RECEPTOR & GLASS WASHER |
| | WITH EITHER A STANDPIPE OR WASTE RECEPTOR. |
| | |
| | 1A)2010 FBC-P 1003.3.5 AUTOMATIC GREASE REMOVAL |
| | DEVICES. WHERE AUTOMATIC GREASE REMOVAL DEVICES ARE |
| | INSTALLED, SUCH DEVICES SHALL BE LOCATED DOWNSTREAM OF |
| | EACH FIXTURE OR MULTIPLE FIXTURES IN ACCORDANCE WITH |
| | THE MANUFACTURER?S INSTRUCTIONS. THE AUTOMATIC GREASE |
| | REMOVAL DEVICE SHALL BE SIZED TO PRETREAT THE MEASURED |
| | OR CALCULATED FLOWS FOR ALL CONNECTED FIXTURES OR |
| | EQUIPMENT. READY ACCESS SHALL BE PROVIDED FOR |
| | INSPECTION AND MAINTENANCE. |
| | |
| | 1B)2010 FBC-P DEFINITIONS: READY ACCESS. THAT WHICH |
| | ENABLES A FIXTURE, APPLIANCE OR EQUIPMENT TO BE |
| | DIRECTLY REACHED WITHOUT REQUIRING THE REMOVAL OR |
| | MOVEMENT OF ANY PANEL, DOOR OR SIMILAR OBSTRUCTION AND |
| | WITHOUT THE USE OF A PORTABLE LADDER, STEP STOOL OR |
| | SIMILAR DEVICE. |
| | |
| | 1C) 2010 FBC-P 802.1.7 COMMERCIAL DISHWASHING MACHINES. |
| | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE |
| | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| | 802.2. |
| | |
| | 1D) 2010 FBC-P 802.2 INSTALLATION. ALL INDIRECT WASTE |
| | PIPING SHALL DISCHARGE THROUGH AN AIR GAP OR AIR BREAK |
| | INTO A WASTE RECEPTOR OR STANDPIPE. WASTE RECEPTORS AND |
| | STANDPIPES SHALL BE TRAPPED AND VENTED AND SHALL |
| | CONNECT TO THE BUILDING DRAINAGE SYSTEM. ALL INDIRECT |
| | WASTE PIPING THAT EXCEEDS 2 FEET (610 MM) IN DEVELOPED |
| | LENGTH MEASURED HORIZONTALLY, OR 4 FEET (1219 MM) IN |
| | TOTAL DEVELOPED LENGTH, SHALL BE TRAPPED. |
| | |
| | THE GLASS WASHER HAS A HEATER IN THE UNIT THAT HAS A |
| | SUSTAINER HEATER THAT PROVIDES 130 DEGREE CONTINIOUS |
| | WATER, IF THE TANKLESS WATER HEATER IS PROVIDING 120 |
| | DEGREE WATER WHAT STOPS THE WATER TO BE HEATED ABOVE |
| | 140 DEGREES? PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-P |
| | |
| | 1E) PLEASE PROVIDE THE SIZE OF THE WASTE BRANCH FOR THE |
| | GREASE INTERCEPTOR, MOP /SERVICE SINK, WASTE RECEPTOR & |
| | GLASS WASHER. 701.7 CONNECTIONS. |
| | DIRECT CONNECTION OF A STEAM EXHAUST, BLOWOFF OR DRIP |
| | PIPE SHALL NOT BE MADE WITH THE BUILDING DRAINAGE |
| | SYSTEM. WASTEWATER WHEN DISCHARGED INTO THE BUILDING |
| | DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER |
| | THAN 140?F (60?C). WHEN HIGHER TEMPERATURES EXIST, |
| | APPROVED COOLING METHODS SHALL BE PROVIDE |
| | |
| | 1F) 2010 FBC-P 803.1 WASTEWATER TEMPERATURE. STEAM |
| | PIPES SHALL NOT CONNECT TO ANY PART OF A DRAINAGE OR |
| | PLUMBING SYSTEM AND WATER ABOVE 140?F (60?C) SHALL NOT |
| | BE DISCHARGED INTO ANY PART OF A DRAINAGE SYSTEM. SUCH |
| | PIPES SHALL DISCHARGE INTO AN INDIRECT WASTE RECEPTOR |
| | CONNECTED TO THE DRAINAGE SYSTEM. |
| | |
| | 2) THE SANITARY ISOMETRIC DOES NOT SHOW THE FLOW |
| | CONTROL DEVICE AND REQUIRED VENT. 2010 FBC-P 1003.3.4.2 |
| | RATE OF FLOW CONTROLS. |
| | GREASE INTERCEPTORS AND GREASE TRAPS SHALL BE EQUIPPED |
| | WITH DEVICES TO CONTROL THE RATE OF WATER FLOW SO THAT |
| | THE WATER FLOW DOES NOT EXCEED THE RATED FLOW. THE |
| | FLOW-CONTROL DEVICE SHALL BE VENTED AND TERMINATE NOT |
| | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD RIM LEVEL |
| | OR BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S |
| | INSTRUCTIONS. |
| | |
| | 3) THE GLASS WASHER, ESPRESSO & COFFEE MAKERS HAVE |
| | CELLINOID VALVES AND WILL NEED TO COMPLY WITH : 2010 |
| | FBC-P 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | |
| | 4) T HE GLASS WASHER, ESPRESSO & COFFEE MAKER WILL ALSO |
| | NEED TO COMPLY WITH 2010 FBC-P 608.16.10 COFFEE |
| | MACHINES AND NONCARBONATED BEVERAGE DISPENSERS. |
| | THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND |
| | NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED |
| | AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO |
| | ASSE 1022 OR BY AN AIR GAP. |
| | |
| | JAMES A. WITMER CBO |