Plan Review Notes
Plan Review Notes For Permit 14040407
Permit Number 14040407
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-07 14:31:01THIS PERMIT IS CONDITINALLY APPROVED AS FOLLOWS:
 ELECTRICAL PROVISOS FOR PERMIT #14040407
 1. ALL AUXILIARY AUDIO SYSTEMS SHALL BE MUTED BY THE
 FIRE ALARM CONTROL PANEL IN THE EVENT OF AN ALARM
 CONDITION.
 2. AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND
 RACEWAY SHALL BE CONSIDERED A WET LOCATION; ALL
 CONDUCTORS WITHIN THE RACEWAY SHALL BE LISTED
 ACCORDINGLY. ALL TRENCHING SHALL REMAIN OPEN FOR
 INSPECTION. NO SITE TUBES ACCEPTED.
 3. UNLESS INSTALLED AND COMPLETED BY THE EC OF RECORD,
 A SEPARATE PERMIT IS REQUIRED FOR ALL LOW VOLTAGE, DATA
 AND/OR COMMUNICATIONS SYSTEMS, INCLUDING FIRE ALARM
 WORK
 4. ALL LOW VOLTAGE & CONTROL OR COMMUNICATION WIRING
 SHALL BE LISTED FOR THE APPLICATION
 5. MISSING EMERGENCY LIGHT IN BATHROOM
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  
  
  