| 2014-05-15 11:28:06 | ELECTRICAL PROVISOS FOR PERMIT #14040385 | | | 1. THOUGH ENERGY CODE COMPLIANCE MAY BE WAIVED DUE TO | | | THE TEMPORARY NATURE OF THE PROJECT, PROPER EMERGENCY & | | | EXIT LIGHTING REQUIREMENTS CAN?T BE WAIVED AND WILL BE | | | EXPECTED FOR FINAL INSPECTIONS. | | | 2. AS PER NEC 210.8(B), ALL 125 V 15 & 20 AMP | | | SINGLE-PHASE RECEPTACLES IN KITCHENS SHALL BE GFCI | | | PROTECTED. | | | 3. PANEL SHALL BE LABELED AS PER NEC 110.16. | | | 4. MAKE SURE THAT THE SERVICE OUTLET OR THE DISCONNECT | | | FOR THE CONDENSING UNITS ARE NOT BLOCKED AS PER NEC | | | 110.26(A) | | | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY TO SEE | | | IF THERE ARE ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|