| 2014-04-26 07:23:19 | PLUMBING PLAN REVIEW |
| | PERMIT: 14040385 |
| | ADD: 8225 IBIS |
| | CONT: TBD |
| | TEL: (561)723-2623/ LARRY ZUBIK |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. APRIL 26/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS DO NOT INDICATE THE AADDITION, DELETIONOF |
| | ANY PLUMBING FIXTURES, SHEET PL201 DOES HAVE A DETAIL |
| | OF STEAM GENERATOR, PLEASE PROVIDE IF THIS UNIT IS GAS |
| | OR ELECTRIC? WHAT THIS UNIT IS TO BE USED FOR? CLEANING |
| | OF GREASY WASTE FROM KITCHEN APPLIANCES OR FOR A DISH |
| | OR GLASS WASHER? 107.2.1.3. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | IF THIS STEAM GENERATOR IS TO BE USED IN CLEANING WITH |
| | A COMMERCIAL DISH OR GLASS WASHER ONE CONCERN WILL BE |
| | COMPLIANCE WITH 2010 FBC-PLUMBING 701.7 CONNECTIONS. |
| | DIRECT CONNECTION OF A STEAM EXHAUST, BLOWOFF OR DRIP |
| | PIPE SHALL NOT BE MADE WITH THE BUILDING DRAINAGE |
| | SYSTEM. WASTEWATER WHEN DISCHARGED INTO THE BUILDING |
| | DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER |
| | THAN 140?F (60?C). WHEN HIGHER TEMPERATURES EXIST, |
| | APPROVED COOLING METHODS SHALL BE PROVIDED. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |