| Plan Review Notes For Permit 14040381 |
| Permit Number |
14040381 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-04-22 14:28:57 | RESIDENTIAL (R3) REROOF, THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- FLAT ROOF (DCA RULE 9N-3): | | | A) NOA 13-0424.14 SUBMITTED ALSO REQUIRES SIGNED AND | | | SEALED RAS 117 CALCULATIONS FOR THE NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS. REQUIRED TO MEET THE DESIGN | | | PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | PROVIDE 2 SIGNED AND SEALED RAS 117 CALCULATIONS. | | | | | | 2- SHINGLES NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE | | | MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND | | | RESUBMIT. (2 COPIES). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|