| Plan Review Notes For Permit 14040381 |
| Permit Number |
14040381 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-21 13:50:18 | RESIDENTIAL (R3) REROOF, SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- FLAT ROOF (DCA RULE 9N-3): | | | A) NOA 13-0204.03 APPROVED ASSEMBLY SUBMITTED REQUIRES | | | SIGNED AND SEALED RAS 117 CALCULATIONS FOR THE NAIL | | | ENHANCING AT PERIMETER AND CORNER AREAS. REQUIRED TO | | | MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010 | | | FBC-RESIDENTIAL. PROVIDE 2 SIGNED AND SEALED RAS 117 | | | CALCULATIONS. | | | | | | B) NOA 13-0204.03 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE | | | MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. PROVIDE 2 | | | COPIES. | | | | | | 2- SHINGLES NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE | | | MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND | | | RESUBMIT. (2 COPIES). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|