| 2014-04-25 13:19:29 | PLUMBING PLAN REVIEW |
| | PERMIT: 14040379 |
| | ADD: 2101 OKEECHOBEE BLVD |
| | CONT: HEDRICK BROTHERS RENE YERNANDEZ CELL 561-568-4182 |
| | TEL: (561)689-8880 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY/ APRIL 25/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET P.01 DOES NOT LIST THE CAR WASH FLOOR DRAIN |
| | NOR IS THE INFORMATION FOUND ON P2.1.3. |
| | 2010 FBC-P 412.1 APPROVAL. |
| | FLOOR DRAINS SHALL CONFORM TO ASME A112.3.1, ASME |
| | A112.6.3 OR CSA B79. TRENCH DRAINS SHALL COMPLY WITH |
| | ASME A112.6.3. |
| | |
| | 412.2 FLOOR DRAINS. |
| | FLOOR DRAINS SHALL HAVE REMOVEABLE STRAINERS. THE FLOOR |
| | DRAIN SHALL BE CONSTRUCTED SO THAT THE DRAIN IS CAPABLE |
| | OF BEING CLEANED. ACCESS SHALL BE PROVIDED TO THE DRAIN |
| | INLET. READY ACCESS SHALL BE PROVIDED TO FLOOR DRAINS. |
| | |
| | 2) SHEET P.02 DETAIL FOR ROOF PIPING SUPPORT, TAN PRO |
| | 801 IS INDICATED TO HAVE MIAMI DADE PRODUCT TEST |
| | REPORT, PLEASE PROVIDE REPORT SHOWING COMPLIANCE WITH |
| | 2010 FBC-P 308.4 STRUCTURAL ATTACHMENT. |
| | HANGERS AND ANCHORS SHALL BE ATTACHED TO THE BUILDING |
| | CONSTRUCTION IN AN APPROVED MANNER. |
| | 308.5 INTERVAL OF SUPPORT. PIPE SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH TABLE 308.5. |
| | |
| | 3) WITHIN THE PERMIT SET OF PLANS THERE ARE NO CIVIL |
| | PLANS OR OVER ALL SITE BUILDING SEWER PLANS PROVIDING A |
| | OVER ALL LAYOUT OF THE VARIOUS BUILDING SEWERS AND HOW |
| | THEY DEVELOP INTO THE BUILDING SEWER PLAN. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5.1.3(4) |
| | BUILDING SEWER, MINIMUM REQUIREMENTS FOR COMMERCIAL |
| | PLUMBING PLAN REVIEW. |
| | |
| | 4) SHEET P2.1.2: |
| | 4A) THE PLANS SHOW CAR LIFTS BUT THERE IS NO MENTION AS |
| | TO WHAT TYPE SYSTEM THESE LIFTS ARE, IF THEY ARE |
| | HYDROLIC, ELECTRIC, PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATIONS AND INSTALATION INFORMATION. CONCERNS |
| | WITH HYDROLIC FLUID LEAKS AND CLEAN UP OF SUCH LEAKS. |
| | THE SAME ISSUE |
| | IS WITH THE PARTS DELIVERY LIFT TO THE MEZANINE LEVEL, |
| | THE STRUCTURAL SHEETS SHOW A RECESS INTHE SLAB. |
| | HYDROLIC LIFTS MAY NEED TO COMPLY WITH 1003.4 OIL |
| | SEPARATORS OR A OIL SEPARATOR IS NOT REQUIRED IN |
| | HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM |
| | IS INSTALLED (EXCEPTION). |
| | |
| | 4B) THIS OCCUPANCY BEING A AUTOMOBILE REPAIR & SERVICE |
| | GARAGE WILL NEED TO SHOW COMPLIANCE WITH 2010 FBC-P |
| | 1003.4.2.2 GARAGES AND SERVICE STATIONS. |
| | WHERE AUTOMOBILES ARE SERVICED, GREASED, REPAIRED OR |
| | WASHED OR WHERE GASOLINE IS DISPENSED, OIL SEPARATORS |
| | SHALL HAVE A MINIMUM CAPACITY OF 6 CUBIC FEET (0.168 |
| | M3) FOR THE FIRST 100 SQUARE FEET (9.3 M2) OF AREA TO |
| | BE DRAINED, PLUS 1 CUBIC FOOT (0.28 M3) FOR EACH |
| | ADDITIONAL 100 SQUARE FEET (9.3 M2) OF AREA TO BE |
| | DRAINED INTO THE SEPARATOR. PARKING GARAGES IN WHICH |
| | SERVICING, REPAIRING OR WASHING IS NOT CONDUCTED, AND |
| | IN WHICH GASOLINE IS NOT DISPENSED, SHALL NOT REQUIRE A |
| | SEPARATOR. AREAS OF COMMERCIAL GARAGES UTILIZED ONLY |
| | FOR STORAGE OF AUTOMOBILES ARE NOT REQUIRED TO BE |
| | DRAINED THROUGH A SEPARATOR. |
| | |
| | 5) SHEET P2.1.3. |
| | 5A) THE PLANS REFERENCE BROADWAY EQUIPMENT CO. BUT NO |
| | FURTHER DIRECTION IS GIVEN WHERE TO FIND DETAILS ON THE |
| | TRENCH DRAIN, NEITHER THE STRUCTURAL PLANS PROVIDE ANY |
| | INFORMATION. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5B) PLEASE PROVIDE A DOMESTIC WATER PLAN FOR THIS |
| | BUILDING SHOW HOW THE POTABLE WATER WILL BE HOOKED INTO |
| | THE CAR WASH RECLAIMED WATER SYSTEM AND PROTECTION OF |
| | THE POTABLE WATER, 2010 FBC-P 608.3 608.3 DEVICES, |
| | APPURTENANCES, APPLIANCES AND APPARATUS. |
| | ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS |
| | INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS |
| | STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR |
| | STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER |
| | SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION |
| | AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY |
| | SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS, |
| | COMMERCIAL DRINKING WATER DISPENSERS AND ALL OTHER |
| | APPLIANCES AND DEVICES THAT HANDLE OR TREAT POTABLE |
| | WATER SHALL BE PROTECTED AGAINST CONTAMINATION. |
| | |
| | 5C) THE PLANS APEAR TO HAVE THE VENT FOR THE OIL |
| | SEPARATOR BUT THERE IS NO VENT SHOWN FOR THE FLOW |
| | CONTROL DEVICE (AIR INTAKE) 2010 FBC-P 1003.3.4.2. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |