2014-05-01 18:40:36FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
 1. THE TWO ROOMS/OFFICES ON THE NE CORNER ARE MISSING
 BOTH EXIT AND/OR EMERGENCY LIGHTING FBC_B 1006.2.1(2)
 2. THE DEDICATED CIRCUIT FOR THE DRINKING FOUNTAIN
 SHALL BE GFCI PROTECTED NEC 422.52
 3. CORRECT KEY NOTE 1 ON PAGE E5.1
 4. THE RISER DIAGRAM FROM DPB OUT HAS TO BE CORRECTED.
 5. INDICATE THE CIRCUIT DESIGNATION FOR THE OUTLETS ON
 THE TELEPHONE RISER DIAGRAM
 6. A SEPARATE PERMIT & SHOP DRAWINGS ARE REQUIRED FOR
 THE FIRE ALARM.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  