| Plan Review Notes For Permit 14040379 |
| Permit Number |
14040379 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-01 18:40:36 | FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS: | | | 1. THE TWO ROOMS/OFFICES ON THE NE CORNER ARE MISSING | | | BOTH EXIT AND/OR EMERGENCY LIGHTING FBC_B 1006.2.1(2) | | | 2. THE DEDICATED CIRCUIT FOR THE DRINKING FOUNTAIN | | | SHALL BE GFCI PROTECTED NEC 422.52 | | | 3. CORRECT KEY NOTE 1 ON PAGE E5.1 | | | 4. THE RISER DIAGRAM FROM DPB OUT HAS TO BE CORRECTED. | | | 5. INDICATE THE CIRCUIT DESIGNATION FOR THE OUTLETS ON | | | THE TELEPHONE RISER DIAGRAM | | | 6. A SEPARATE PERMIT & SHOP DRAWINGS ARE REQUIRED FOR | | | THE FIRE ALARM. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|