2014-06-12 12:44:50PROJECT: SPORTS AUTHORITY, 1875 PALM BEACH LAKES BLVD.
 PERMIT#:14040359
 DATE: 06/12/14
 CODE: 2008 EDITION OF THE NEC.
 2010 EDITION OF THE FBC,
 2010 EDITION OF THE WPB AMENDMENTS TO THE FBC, CHAPTER
 1, ADMINISTRATION
 2ND ELECTRICAL REVIEW
  
 ACTION: ELECTRICAL PROVISO:
  
 1) PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR
 LIGHTING CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH
 THE FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS
 SHALL BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY 505.2
  
 2) PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT.
 AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY
 CONSERVATION 505.2
  
 3) PROVIDE PLAQUES FOR THE ELECTRICAL SERVICE DENOTING
 WHERE ALL OTHER SERVICES AND MAINS FEEDING THE BUILDING
 ARE LOCATED. NEC 230.2(E)
  
 4) A PERMANENT PLAQUE OR DIRECTORY, DENOTING ALL
 ELECTRIC POWER SOURCES ON OR IN THE PREMISES, SHALL BE
 INSTALLED AT EACH SERVICE EQUIPMENT LOCATION AND AT
 LOCATIONS OF ALL ELECTRIC POWER PRODUCTION SOURCES
 CAPABLE OF BEING INTERCONNECTED. A SIGN SHALL BE PLACED
 AT THE SERVICE ENTRANCE INDICATING TYPE AND LOCATION OF
 ON-SITE STANDBY POWER SOURCES. NEC 700, 701.9, AND
 705.10
  
 CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED
 AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP
 OR WET LOCATIONS. NEC 110.3, 110.8,
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR,
 GENERATORS, FIRE ALARM SYSTEMS, SECURITY, VOICE, AND
 DATA SYSTEMS
  