| 2014-06-12 12:44:50 | PROJECT: SPORTS AUTHORITY, 1875 PALM BEACH LAKES BLVD. |
| | PERMIT#:14040359 |
| | DATE: 06/12/14 |
| | CODE: 2008 EDITION OF THE NEC. |
| | 2010 EDITION OF THE FBC, |
| | 2010 EDITION OF THE WPB AMENDMENTS TO THE FBC, CHAPTER |
| | 1, ADMINISTRATION |
| | 2ND ELECTRICAL REVIEW |
| | |
| | ACTION: ELECTRICAL PROVISO: |
| | |
| | 1) PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR |
| | LIGHTING CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH |
| | THE FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS |
| | SHALL BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| | 10 HOURS. FBC ENERGY 505.2 |
| | |
| | 2) PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT. |
| | AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING |
| | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER |
| | FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY |
| | CONSERVATION 505.2 |
| | |
| | 3) PROVIDE PLAQUES FOR THE ELECTRICAL SERVICE DENOTING |
| | WHERE ALL OTHER SERVICES AND MAINS FEEDING THE BUILDING |
| | ARE LOCATED. NEC 230.2(E) |
| | |
| | 4) A PERMANENT PLAQUE OR DIRECTORY, DENOTING ALL |
| | ELECTRIC POWER SOURCES ON OR IN THE PREMISES, SHALL BE |
| | INSTALLED AT EACH SERVICE EQUIPMENT LOCATION AND AT |
| | LOCATIONS OF ALL ELECTRIC POWER PRODUCTION SOURCES |
| | CAPABLE OF BEING INTERCONNECTED. A SIGN SHALL BE PLACED |
| | AT THE SERVICE ENTRANCE INDICATING TYPE AND LOCATION OF |
| | ON-SITE STANDBY POWER SOURCES. NEC 700, 701.9, AND |
| | 705.10 |
| | |
| | CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED |
| | AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP |
| | OR WET LOCATIONS. NEC 110.3, 110.8, |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, |
| | GENERATORS, FIRE ALARM SYSTEMS, SECURITY, VOICE, AND |
| | DATA SYSTEMS |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER PX3421, |
| | 561-805-6717, [email protected] |
| | |