| | SPORTS AUTHORITY |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| | 505.5.3; T. 505.5.3 |
| | |
| | PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR |
| | LIGHTING CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH |
| | THE FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS |
| | SHALL BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| | 10 HOURS. FBC ENERGY CONSERVATION 505.2 |
| | |
| | PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT. |
| | AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING |
| | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER |
| | FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY |
| | CONSERVATION 505.2 |
| | |
| | THE MASTER PLAN FOR BUILDINGS ?A?, ?B?, ?C?, LIMIT THE |
| | NUMBER OF MAIN DISCONNECTS WHICH MAY BE GROUPED IN ONE |
| | LOCATION. SHOW LOCATION OF THE MAIN SERVICE WITH |
| | DISCONNECTS GROUPED FOR THIS BUILDING. SHOW LOCATION OF |
| | THE EXISTING MAINS RELATIVE TO THE ELECTRIC SERVICE |
| | PROPOSED FOR SPORTS AUTHORITY. NEC 230.2; 230.40; |
| | 230.70; 230.71 |
| | |
| | PROVIDE PLAQUES FOR THE ELECTRICAL SERVICE DENOTING |
| | WHERE ALL OTHER SERVICES AND MAINS FEEDING THE BUILDING |
| | ARE LOCATED. NEC 230.2(E) |
| | |
| | PROVIDE A DETAIL SHOWING STRAIN RELIEVE DEVICES FOR SO |
| | CORD CONNECTIONS. NEC 400.10 |
| | |
| | PROVIDE THE SPECIFICATIONS AND LISTING FOR THE ATS. NEC |
| | 110.3 |
| | |
| | RECEPTACLES LOCATED WITHIN 6 FEET OF SINKS MUST BE GFCI |
| | PROTECTED. NEC 210.8 |
| | |
| | RECEPTACLES ON ROOF REQUIRE GFCI PROTECTION. NEC 210.8; |
| | 210.63 |
| | |
| | CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED |
| | AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP |
| | OR WET LOCATIONS. NEC 110.3, 110.8, |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, |
| | GENERATORS, FIRE ALARM SYSTEMS, SECURITY, VOICE, AND |
| | DATA SYSTEMS |
| | |