2014-04-11 06:56:44FUEL GAS/ PLUMBING PLAN REVIEW
 PERMIT: 14040355
 ADD: 1177 CLARE AVE
 CONT:L & R GAS CONTRACTORS
 TEL: (561)776-6035
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY APRIL 11/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 105.1
 REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT AUTHORIZED IN
 ACCORDANCE WITH FLORIDA STATUTE 489 WHO INTENDS TO
 CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR
 CHANGE THE OCCUPANCY OF A BUILDING OR STRUCTURE, OR TO
 ERECT, INSTALL, ENLARGE, ALTER, REPAIR, REMOVE, CONVERT
 OR REPLACE ANY IMPACTRESISTANT COVERINGS, ELECTRICAL,
 GAS, MECHANICAL, PLUMBING OR FIRE PROTECTION SYSTEM, OR
 ACCESSIBLE OR FLOOD RESISTANT SITE ELEMENT, THE
 INSTALLATION OF WHICH IS REGULATED BY THIS CODE, OR TO
 CAUSE ANY SUCH WORK TO BE DONE, SHALL FIRST MAKE
 APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE
 REQUIRED PERMIT.
  
 1A) WITH THE NEW GAS APPLIANCES BEING INTRODUCED INTO
 THIS DELI / CAFE A GREASE INTERCEPTOR PERMIT WILL BE
 REQUIRED, 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION 107.3.5.1.3(11).
  
 1B) THE PLANS SUBMITTED FOR THE NEW GAS APPLIANCES WILL
 NEED TO PROVIDE A FLOOR PLAN AND SANITARY RISER DIAGRAM
 FOR ALL PLUMBING FIXTURES. IT APPEARS THIS MAY BE A
 CHANGE IN OCCUPANCY. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5.1.3 PLUMBING (4) SANITARY, (6) VENTS & (1)
 MINIMUM PLUMBING FIXTURES .
  
 1C) THIS TENNANCY AND USE OF THIS PORTION OF THE
 BUILDING WILL REQUIRE A SERVICE SINK FOR THE REMOVAL OF
 GREASY WASTE FROM ON THE FLOOR. 2010 FBC-P 403.1.3.1(2)
 & TABLE 403.1(1)A-2.
  
 2) GAS PERIMT MISSING PLAN REVIEW CRITERIA:
 107.3.5.1.5
  
 2.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS. PLANS INDICATE THE USE OF A 2 LB
 REGULATOR BUT NO MANUFACTURERS CUT SHEETS WERE
 SUBMITTED ON THE 2 LB REGULATOR.
  
 2.2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER