| 2014-04-11 06:56:44 | FUEL GAS/ PLUMBING PLAN REVIEW |
| | PERMIT: 14040355 |
| | ADD: 1177 CLARE AVE |
| | CONT:L & R GAS CONTRACTORS |
| | TEL: (561)776-6035 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY APRIL 11/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 105.1 |
| | REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT AUTHORIZED IN |
| | ACCORDANCE WITH FLORIDA STATUTE 489 WHO INTENDS TO |
| | CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR |
| | CHANGE THE OCCUPANCY OF A BUILDING OR STRUCTURE, OR TO |
| | ERECT, INSTALL, ENLARGE, ALTER, REPAIR, REMOVE, CONVERT |
| | OR REPLACE ANY IMPACTRESISTANT COVERINGS, ELECTRICAL, |
| | GAS, MECHANICAL, PLUMBING OR FIRE PROTECTION SYSTEM, OR |
| | ACCESSIBLE OR FLOOD RESISTANT SITE ELEMENT, THE |
| | INSTALLATION OF WHICH IS REGULATED BY THIS CODE, OR TO |
| | CAUSE ANY SUCH WORK TO BE DONE, SHALL FIRST MAKE |
| | APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE |
| | REQUIRED PERMIT. |
| | |
| | 1A) WITH THE NEW GAS APPLIANCES BEING INTRODUCED INTO |
| | THIS DELI / CAFE A GREASE INTERCEPTOR PERMIT WILL BE |
| | REQUIRED, 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION 107.3.5.1.3(11). |
| | |
| | 1B) THE PLANS SUBMITTED FOR THE NEW GAS APPLIANCES WILL |
| | NEED TO PROVIDE A FLOOR PLAN AND SANITARY RISER DIAGRAM |
| | FOR ALL PLUMBING FIXTURES. IT APPEARS THIS MAY BE A |
| | CHANGE IN OCCUPANCY. 2010 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5.1.3 PLUMBING (4) SANITARY, (6) VENTS & (1) |
| | MINIMUM PLUMBING FIXTURES . |
| | |
| | 1C) THIS TENNANCY AND USE OF THIS PORTION OF THE |
| | BUILDING WILL REQUIRE A SERVICE SINK FOR THE REMOVAL OF |
| | GREASY WASTE FROM ON THE FLOOR. 2010 FBC-P 403.1.3.1(2) |
| | & TABLE 403.1(1)A-2. |
| | |
| | 2) GAS PERIMT MISSING PLAN REVIEW CRITERIA: |
| | 107.3.5.1.5 |
| | |
| | 2.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 FUEL GAS. PLANS INDICATE THE USE OF A 2 LB |
| | REGULATOR BUT NO MANUFACTURERS CUT SHEETS WERE |
| | SUBMITTED ON THE 2 LB REGULATOR. |
| | |
| | 2.2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |