Plan Review Notes
Plan Review Notes For Permit 14040298
Permit Number 14040298
Review Stop R
Sequence Number 1
Notes
Date Text
2014-08-27 18:17:00SEPARATE PERMIT REQUIRED FOR ROOF
 ASSEMBLY SELECTED HAD A LIMITATION OF -52.5. ZONE 1
 REQUIREMENT IS 59.38. SEE RAS 117 8.1, DESIGN PRESSURE
 FOR THE SELECTED ASSEMBLY IS TO APPLY TO ZONE 1.
  
  