Plan Review Notes
Plan Review Notes For Permit 14040298
Permit Number 14040298
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-07 17:37:58FAILED ELECTRICAL REVIEW 5/7/14
  
 1 APPLICABLE ELECTRICAL CODE IN FORCE IS THE 2008
 EDITION OF THE NEC
 2. ARC-FAULT REQUIREMENTS AS PER THE CURRENT CODE DO
 NOT MATCH THE NOTES AS SUBMITTED.
 3. NEED BETTER DETAIL ON THE ELECTRICAL PAGE TO SHOW
 WHAT AREA WILL BE ENCLOSED AND WHAT WILL BE OPEN.
 4. ALL EXTERIOR OUTLETS SHALL BE GFCI PROTECTED.
 5. THE DISCONNECT FOR THE CONDENSING UNIT SHALL BE
 WITHIN SIGHT OF EQUIPMENT.
 6. THE SERVICED OUTLET REQUIRED BY 210.63 SHALL NOT BE
 BEHIND THE UNIT.
 7. MAKE MENTION OF THE NEC 314.27(A) REQUIREMENT FOR
 THE CEILING BOXES.
  
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  