| Notes |
| Date |
Text |
| 2014-05-07 17:37:58 | FAILED ELECTRICAL REVIEW 5/7/14 | | | | | | 1 APPLICABLE ELECTRICAL CODE IN FORCE IS THE 2008 | | | EDITION OF THE NEC | | | 2. ARC-FAULT REQUIREMENTS AS PER THE CURRENT CODE DO | | | NOT MATCH THE NOTES AS SUBMITTED. | | | 3. NEED BETTER DETAIL ON THE ELECTRICAL PAGE TO SHOW | | | WHAT AREA WILL BE ENCLOSED AND WHAT WILL BE OPEN. | | | 4. ALL EXTERIOR OUTLETS SHALL BE GFCI PROTECTED. | | | 5. THE DISCONNECT FOR THE CONDENSING UNIT SHALL BE | | | WITHIN SIGHT OF EQUIPMENT. | | | 6. THE SERVICED OUTLET REQUIRED BY 210.63 SHALL NOT BE | | | BEHIND THE UNIT. | | | 7. MAKE MENTION OF THE NEC 314.27(A) REQUIREMENT FOR | | | THE CEILING BOXES. | | | | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | | | | |
|