| Plan Review Notes For Permit 14040255 |
| Permit Number |
14040255 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-07 16:11:03 | BUILDING REVISION COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- A) REVISE ENERGY CALCULATIONS SUBMITTED FOR THE MAIN | | | HOUSE. THE AREA-WEIGHTED AVERAGE MAXIMUM FENESTRATION | | | SHGC PERMITTED SHALL BE 0.50. SEE SECTION 402.5 OF 2010 | | | FBC-ENERGY CONSERVATION. THIS IS REQUIRED BY SEC. | | | 405.2. ENERGY CALCULATIONS SUBMITTED SHOW 0.640. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ENTRY DOORS WITH SIZE (3'-6" X 8'-0") AND WITH | | | SIDELITES AS SHOWN ON PLANS. AND TYPE OF DOOR (WOOD) AS | | | SPECIFIED ON DOOR SCHEDULE. | | | | | | 3- NEW ITEM: ENTRY DOOR WITH HURRICANE SHUTTERS. | | | PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION | | | SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|