2014-04-07 16:11:03BUILDING REVISION COMMENTS.
 CODE: 2010 FBC.
  
 1- A) REVISE ENERGY CALCULATIONS SUBMITTED FOR THE MAIN
 HOUSE. THE AREA-WEIGHTED AVERAGE MAXIMUM FENESTRATION
 SHGC PERMITTED SHALL BE 0.50. SEE SECTION 402.5 OF 2010
 FBC-ENERGY CONSERVATION. THIS IS REQUIRED BY SEC.
 405.2. ENERGY CALCULATIONS SUBMITTED SHOW 0.640.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOORS WITH SIZE (3'-6" X 8'-0") AND WITH
 SIDELITES AS SHOWN ON PLANS. AND TYPE OF DOOR (WOOD) AS
 SPECIFIED ON DOOR SCHEDULE.
  
 3- NEW ITEM: ENTRY DOOR WITH HURRICANE SHUTTERS.
 PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  