Plan Review Notes
Plan Review Notes For Permit 14040208
Permit Number 14040208
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-18 14:28:59 
  
  
 BUILDING PROVISO:
 708.14.1 ELEVATOR LOBBY.
 THE REQUIREMENTS IN SECTION 709 FOR FIRE PARTITIONS,
 DOORS PROTECTING OPENINGS IN
 THE ELEVATOR LOBBY ENCLOSURE WALLS SHALL ALSO COMPLY
 WITH SECTION 715.4.3 AS
 REQUIRED FOR CORRIDOR WALLS AND PENETRATIONS OF THE
 ELEVATOR LOBBY ENCLOSURE.
  
 715.4.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE
 BARRIERS.
 FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE
 PROTECTION RATING OF
 20 MINUTES (TABLE 715.4) WHERE LOCATED IN CORRIDOR
 WALLS OR SMOKE BARRIER WALLS
 HAVING A FIRE-RESISTANCE RATING IN ACCORDANCE WITH
 TABLE 715.4 SHALL BE TESTED IN
 ACCORDANCE WITH NFPA 252 OR UL 10C WITHOUT THE HOSE
 STREAM TEST.