Plan Review Notes
Plan Review Notes For Permit 14040199
Permit Number 14040199
Review Stop M
Sequence Number 3
Notes
Date Text
2014-06-25 14:15:25MECHANICAL REVISION THIRD CHECKLIST.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
  
 A) CALCULATIONS CAN NOT BE DONE FOR WORST CASE
 SCENARIO. SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 REVISE CALCULATIONS AS REQUIRED TO MATCH THE ACTUAL
 BUILDING ORIENTATION.
 ***NOTE: COORDINATE EQUIPMENT OF REVISED CALCULATIONS
 WITH EQUIPMENT SHOWN ON THE A/C PLAN.
  
 *****RESPONSE TO INFORMATION SUBMITTED:
 (1) EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE AGAIN
 DONE BASED ON WORST CASE SCENARIO. NEED TO USE THE
 ACTUAL BUILDING ORIENTATION. THERE IS NOT NW, NE, SE,
 SW, SE, SW ORIENTATION FOR THIS HOUSE. SEE PLANS AND
 REVISE AS REQUIRED.
 SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 (2) THERE IS NOT GARAGE IN THIS HOUSE. THEREFORE, THERE
 ARE NOT ADJACENT WALLS EITHER. SEE PLANS AND REVISE
 CALCULATIONS AS REQUIRED. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 (3) THERE ARE NOT 34 OCCUPANTS IN A SINGLE FAMILY
 RESIDENCE OF 3 BEDROOMS. SEE PLANS AND REVISE
 CALCULATIONS AS REQUIRED. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 (4) A/C EQUIPMENT SELECTED (OUTDOOR AND INDOOR) :
 PROVIDE THE MANUFACTURER'S PUBLISHED AHRI CERTIFICATE
 SHOWING THE SENSIBLE AND TOTAL COOLING CAPACITY AS
 REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
  
 B) OK. HOUSE ADDRESS WAS CORRECTED.
  
 C) COOLING AND HEATING INFORMATION SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS DON'T MATCH THE
 INFORMATION SHOWN ON THE ENERGY CALCULATIONS SUBMITTED.
 REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION. ***(REPEAT COMMENT. NOT
 ADDRESSED).
  
 2- A/C CONTRACTOR RESPONSIBLE FOR THE DESIGN OF THE A/C
 PLAN SUBMITTED TO PROVIDE NAME AND SIGNATURE AS
 REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
 ***(REPEAT COMMENT. NOT ADDRESSED).
  
  
 3- ENERGY CALCULATIONS SUBMITTED:
  
 A) OK. HOUSE ADDRESS WAS CORRECTED.
  
 B) COOLING AND HEATING INFORMATION DON'T MATCH THE
 HEATING AND COOLING INFORMATION SHOWN ON THE EQUIPMENT
 SIZING CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 C) OK. OWNER/AGENT SIGNED BOTTOM OF FORM.
  
 4- OWES $51.50 FOR REVISON FEES RESUBMITTAL.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER