| 2014-06-25 14:15:25 | MECHANICAL REVISION THIRD CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED: |
| | |
| | A) CALCULATIONS CAN NOT BE DONE FOR WORST CASE |
| | SCENARIO. SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. |
| | REVISE CALCULATIONS AS REQUIRED TO MATCH THE ACTUAL |
| | BUILDING ORIENTATION. |
| | ***NOTE: COORDINATE EQUIPMENT OF REVISED CALCULATIONS |
| | WITH EQUIPMENT SHOWN ON THE A/C PLAN. |
| | |
| | *****RESPONSE TO INFORMATION SUBMITTED: |
| | (1) EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE AGAIN |
| | DONE BASED ON WORST CASE SCENARIO. NEED TO USE THE |
| | ACTUAL BUILDING ORIENTATION. THERE IS NOT NW, NE, SE, |
| | SW, SE, SW ORIENTATION FOR THIS HOUSE. SEE PLANS AND |
| | REVISE AS REQUIRED. |
| | SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | (2) THERE IS NOT GARAGE IN THIS HOUSE. THEREFORE, THERE |
| | ARE NOT ADJACENT WALLS EITHER. SEE PLANS AND REVISE |
| | CALCULATIONS AS REQUIRED. SEC. 103.2.1.1.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | (3) THERE ARE NOT 34 OCCUPANTS IN A SINGLE FAMILY |
| | RESIDENCE OF 3 BEDROOMS. SEE PLANS AND REVISE |
| | CALCULATIONS AS REQUIRED. SEC. 103.2.1.1.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | (4) A/C EQUIPMENT SELECTED (OUTDOOR AND INDOOR) : |
| | PROVIDE THE MANUFACTURER'S PUBLISHED AHRI CERTIFICATE |
| | SHOWING THE SENSIBLE AND TOTAL COOLING CAPACITY AS |
| | REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | |
| | B) OK. HOUSE ADDRESS WAS CORRECTED. |
| | |
| | C) COOLING AND HEATING INFORMATION SHOWN ON THE |
| | EQUIPMENT SIZING CALCULATIONS DON'T MATCH THE |
| | INFORMATION SHOWN ON THE ENERGY CALCULATIONS SUBMITTED. |
| | REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. ***(REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | 2- A/C CONTRACTOR RESPONSIBLE FOR THE DESIGN OF THE A/C |
| | PLAN SUBMITTED TO PROVIDE NAME AND SIGNATURE AS |
| | REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC. |
| | ***(REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED: |
| | |
| | A) OK. HOUSE ADDRESS WAS CORRECTED. |
| | |
| | B) COOLING AND HEATING INFORMATION DON'T MATCH THE |
| | HEATING AND COOLING INFORMATION SHOWN ON THE EQUIPMENT |
| | SIZING CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC. |
| | 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | C) OK. OWNER/AGENT SIGNED BOTTOM OF FORM. |
| | |
| | 4- OWES $51.50 FOR REVISON FEES RESUBMITTAL. |
| | |
| | |
| | |