| Plan Review Notes For Permit 14040199 |
| Permit Number |
14040199 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-11 13:10:00 | REVISION MECHANICAL REVIEW COMMENTS: | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC. | | | 403.6 OF 2010 FBC-ENERGY CONSERVATION. (REQUESTED ON | | | PROVISO DATED 2/7/14, BUT IT WAS NEVER SUBMITTED). | | | | | | ***NOTE: EQUIPMENT SHOWN ON THE CALCULATIONS TO MATCH | | | EQUIPMENT SHOWN ON THE A/C PLAN. | | | | | | | | | 2- A/C CONTRACTOR RESPONSIBLE FOR THE DESIGN OF THE A/C | | | PLAN SUBMITTED TO PROVIDE NAME AND SIGNATURE AS | | | REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (5610805-6712 |
|