2014-04-11 13:10:00REVISION MECHANICAL REVIEW COMMENTS:
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC.
 403.6 OF 2010 FBC-ENERGY CONSERVATION. (REQUESTED ON
 PROVISO DATED 2/7/14, BUT IT WAS NEVER SUBMITTED).
  
 ***NOTE: EQUIPMENT SHOWN ON THE CALCULATIONS TO MATCH
 EQUIPMENT SHOWN ON THE A/C PLAN.
  
  
 2- A/C CONTRACTOR RESPONSIBLE FOR THE DESIGN OF THE A/C
 PLAN SUBMITTED TO PROVIDE NAME AND SIGNATURE AS
 REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (5610805-6712