Plan Review Notes
Plan Review Notes For Permit 14040187
Permit Number 14040187
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-14 13:40:58AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND
 RACEWAY SHALL BE CONSIDERED A WET LOCATION; ALL
 CONDUCTORS WITHIN THE RACEWAY SHALL BE LISTED
 ACCORDINGLY.
 ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION.
 NO SITE TUBES WILL BE ACCEPTED.
 AS PER NEC 300.5(D)(3) A WARNING RIBBON SHALL BE
 PLACED NO MORE THAN 12" ABOVE RACEWAY INSIDE
 TRENCH
  