| Notes |
| Date |
Text |
| 2014-11-21 13:48:18 | ROUTE TO MISC. 1 | | | | | | 11/21/14 APPROVED WITH EXCEPTION. | | | THIS APPLICATION WAS SUBMITTED WITHOUT ALL THE REQUIRED | | | DOCUMENTATION: | | | 1.PROVIDE SPEC SHEETS FOR THE POLES AS WELL AS FOR THE | | | PROPOSED HEADS. | | | 2. PROVIDE ENGINEERED WIND LOAD CALCULATIONS OF THE | | | POLES WITH THE RESPECTIVE HEADS ATTACHED. FBC-1609 | | | 3. COMPLY WITH ALL THE REQUIREMENTS OF THE FBC-ENERGY | | | CONSERVATION REQUIREMENTS FOR EXTERIOR LIGHTING. FBC-E | | | 505.2.4 | | | 4. VERIFY EXISTING WIRING COMPLIES WITH NEC 300.5(B). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT DAVID HAYES (561) 805-6717 |
|