Plan Review Notes
Plan Review Notes For Permit 14040174
Permit Number 14040174
Review Stop B
Sequence Number 3
Notes
Date Text
2014-12-01 09:58:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ENGINEERING PREVIOUSLY PROVIDED (NOW WITH THE
 VOIDED OLD SET OF PLANS) DOES NOT MATCH THE PLANS AND
 IT IS NOT CLEAR WHETHER THE SAME POLE IS PROPOSED.
  
 ENGINEER OF RECORD IS TO REVIEW DELEGATED ENGINEERING,
 SEE FAC61G15. THIS MAY BE DONE BY INCORPORATING A
 REFERENCE TO THE ENGINEERING INTO THE PLAN, A SHOP
 DRAWING REVIEW STAMP, OR BY LETTER.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. VALUE
 IS TO INCLUDE LABOR, MATERIALS, ENGINEERING, OVERHEAD
 AND PROFIT FBC 109.
  
 3. PLEASE NOTE THAT THE POLE ENGINEERING WAS APPROVED
 WITH PROVISO. FIXTURE CALCS WERE TO BE SUBMITTED AS A
 REVISION SUBJECT TO FIELD INSPECTOR'S DISCRETION. THIS
 MAY BE SUBMITTED AT THIS TIME (BUT IS NOT REQUIRED).
  
 4. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED
 SETS FOR PERMIT ISSUANCE. IF THE PREVIOUSLY REVIEWED
 POLE CALCS ARE TO BE A PART OF THE ISSUED PERMIT,
 PLEASE INCLUDE WITH THE NEW SETS. PLEASE DO NOT REMOVE
 ANY OLD SHEETS FROM THE PACKAGE.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved