| Date |
Text |
| 2014-07-07 10:21:19 | FAILED |
| | |
| | 1) PROVIDE A RECENT SURVEY, LESS THAN ONE YEAR OLD, |
| | WHICH INCLUDES THE LOCATIONS OF THE EXISTING TREES |
| | ALONG LAKE AVENUE AND THE EXISTING LIGHT POLES. THE |
| | SURVEY SHALL BE TO SCALE WITH ALL DIMENSION LINES |
| | SHOWN. |
| | |
| | 2) THE SITE PLAN (OR MARKED UP SURVEY) SHALL SHOW THE |
| | PROPOSED NEW AND REPLACEMENT LIGHT POLES WITH THEIR |
| | DIMENSIONS FROM THE PROPERTY LINES. PLEASE NOTE THAT |
| | NEW AND REPLACEMENT POLES SHALL BE LOCATED A MINIMUM OF |
| | 5 FEET FROM THE PROPERTY LINE. |
| | |
| | 3) ONE OF THE NEW POLES ALONG LAKE AVENUE APPEARS THAT |
| | IT WOULD CONFLICT WITH AN EXISTING TREE. THE POLES |
| | SHALL BE PLACED TO AVOID TREES AND THEIR CANOPY GROWTH. |
| | |
| | 4) THE SOUTHERN A2 POST APPEARS THAT IT IS NOT ON |
| | PARCEL 74434404000020020, BUT RATHER PARCEL |
| | 74434404000020010. THIS WILL BE VERIFIED WITH THE |
| | SURVEY. IF THE POST IS ON THE NEIGHBORING PARCEL, THEN |
| | A SEPARATE PERMIT APPLICATION FOR THE WORK ON THE 2ND |
| | PARCEL IS REQUIRED. THE SAME PLANS MAY BE USED FOR |
| | BOTH. |
| | |
| | 5) THE PHOTOMETRIC PLAN SHALL CLEARLY SHOW THE |
| | CENTERLINE OF LAKE AVENUE. HALF OF LAKE AVENUE ABUTTING |
| | THE SOUTH PORTION OF THE SITE IS RESIDENTIALLY ZONED. |
| | THE PHOTOMETRIC CALCULATIONS SHALL BE PROVIDED TO THE |
| | MIDPOINT OF LAKE AVENUE AND SHALL NOT EXCEED 0.5 |
| | FOOTCANDLES. THE PROVIDED PHOTOMETRIC PLAN SEEMS TO |
| | INDICATE HIGHER LIGHT LEVELS. |
| | |
| | 6) THE LIGHT FIXTURES SHALL BE DESIGNED SO THAT GLARE |
| | DOES NOT SPILL INTO THE RIGHT-OF-WAY (DRIVERS VISION). |
| | PLEASE PROVIDE INFORMATION HOW GLARE WILL BE |
| | CONTROLLED. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |