| 2014-12-01 10:14:47 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. THE ENGINEERING PREVIOUSLY PROVIDED (NOW WITH THE |
| | VOIDED OLD SET OF PLANS) DOES NOT MATCH THE PLANS AND |
| | IT IS NOT CLEAR WHETHER THE SAME POLE IS PROPOSED, FBC |
| | 1609. |
| | |
| | ENGINEER OF RECORD IS TO REVIEW DELEGATED ENGINEERING, |
| | SEE FAC61G15. THIS MAY BE DONE BY INCORPORATING A |
| | REFERENCE TO THE ENGINEERING INTO THE PLAN, A SHOP |
| | DRAWING REVIEW STAMP, OR BY LETTER. |
| | |
| | PLEASE NOTE THAT THE ENGINEERING PROVIDED BY MOLNAR |
| | JORDAN & ASSOCIATES SPECIFIES 6' EMBEDMENT, ENGINEERING |
| | BY CHRIS ARLANDSON SPECIFIES 7' EMBEDMENT. THE DESIGNER |
| | OF RECORD HAS NOT INCLUDED WIND DESIGN CRITERIA. WIND |
| | DESIGN CRITERIA IS INCLUDED ON WHAT I ASSUMED WAS |
| | DELEGATED ENGINEERING, BUT THAT IS NOW A PART OF THE |
| | VOIDED PLANS. |
| | |
| | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. VALUE |
| | IS TO INCLUDE LABOR, MATERIALS, ENGINEERING, OVERHEAD |
| | AND PROFIT FBC 109. |
| | |
| | 3. PLEASE NOTE THAT THE POLE ENGINEERING WAS APPROVED |
| | WITH PROVISO. FIXTURE CALCS WERE TO BE SUBMITTED AS A |
| | REVISION SUBJECT TO FIELD INSPECTOR'S DISCRETION. THIS |
| | MAY BE SUBMITTED AT THIS TIME (BUT IS NOT REQUIRED). |
| | |
| | 4. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED |
| | SETS FOR PERMIT ISSUANCE. IF THE PREVIOUSLY REVIEWED |
| | POLE CALCS ARE TO BE A PART OF THE ISSUED PERMIT, |
| | PLEASE INCLUDE WITH THE NEW SETS. PLEASE DO NOT REMOVE |
| | ANY OLD SHEETS FROM THE PACKAGE. |
| | |
| | |
| | |