| 2014-04-28 07:28:59 | PLUMBING PLAN REVIEW |
| | PERMIT: 14040162 |
| | ADD: 1855 PALM BEACH LAKES SUITE # B10 |
| | CONT: TBD |
| | TEL: (561) 373-3902 KARI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. APRIL 28/2014 |
| | ACTION: DENIED |
| | |
| | 1) P5.1 SANITARY WASTE STICK. ELECTRIC WATER HEATER PAN |
| | IS SHOWN TO TIE DIRECTLY INTO THE BUILDING DRAIN. |
| | DISCREPANCY, 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION 107.2.1.3 THE WRITEN DESCRIPTION UNDERTHE |
| | HEADING PLUMBING FIXTURE SCHEDULE WH-1 INDICATES A 3/4 |
| | INCH DRAIN FROM THE PAN TO THE JR-1. |
| | |
| | 2) SHEET P5.1 UNDER THE HEADING PLUMBING FIXTURE |
| | SCHEDULE FD-1 FLOOR DRAIN INDICATES THE USE OF ATRAP |
| | GAURD DEVICE INSTEAD OF A TRAP PRIMER. |
| | |
| | 1002.3 PROHIBITED TRAPS. |
| | THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS |
| | THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEAL. |
| | |
| | 1002.4 TRAP SEALS. |
| | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS |
| | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 |
| | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO |
| | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO |
| | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| | ASSE 1044. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |