| | DSW |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | SJ CORDS ARE NOT ACCEPTABLE AS A WIRING METHOD TO |
| | INTERCONNECT THE LIGHTING FIXTURES. NEC 400.8 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; 505.5.3; T |
| | 505.5.3 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING |
| | CLEARANCE AND DIMENSIONS FOR THE SWITCH BOARDS AND |
| | PANEL BOARDS. 110.26 |
| | |
| | PROVIDE SPECIFICATIONS AND LISTING FOR THE IFS MAIN |
| | DISTRIBUTION EQUIPMENT SPECIFIED AND SHOWN AS EXISTING. |
| | NEC 110.3 |
| | |
| | THE MASTER PLAN FOR BUILDING 'B' LIMITS THE NUMBER OF |
| | MAIN DISCONNECTS WHICH MAY BE GROUPED IN ONE LOCATION. |
| | SHOW LOCATION OF THE MAIN SERVICE WITH DISCONNECTS NEC |
| | 230.2; 230.40; 230.70; 230.71 |
| | |
| | PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF ROOF TOP |
| | EQUIPMENT. NEC 210.8; 210.63 |
| | |
| | VENDING MACHINES REQUIRE GFCI PROTECTION. NEC 422.51 |
| | |
| | PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR |
| | LIGHTING CONTROLS PROVIDED ARE IN ACCORDANCE WITH THE |
| | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL |
| | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| | 10 HOURS. FBC ENERGY CONSERVATION 505.2 |
| | |
| | PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT. |
| | AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING |
| | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER |
| | FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY |
| | CONSERVATION 505.2 |
| | |
| | CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED |
| | AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP |
| | OR WET LOCATIONS. NEC 110.3, 110.8, |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE |
| | ALARM SYSTEMS, SECURITY, VOICE, AND DATA SYSTEMS |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS REVIEW |
| | 561-373-3701 |
| | |
| | |