| 2014-04-28 05:55:13 | BUILDING PLAN REVIEW |
| | PERMIT: 14040161 |
| | ADD: 1865 PALM BEACH LAKES SUITE # ???????? |
| | CONT: TBD |
| | TEL: (561) 373-3902 KARI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. APRIL 28/2014 |
| | ACTION: DENIED |
| | |
| | 1) PB OUTLET MALLS: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER. |
| | |
| | 2) PLANS HAVE NOT BEEN STAMPED WITH THE APPROVED STAMP |
| | FROM NEW ENGLAND DEVELOPMENT PALM BEACH OUTLET SKYE |
| | GROUP TENANT COORDINATION STAMP. |
| | |
| | 3) PLANS AND PERMIT APPLICATION FAIL TO PROVIDE WHAT |
| | THE SUITE NUMBER IS FOR THIS LOCATION. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION, 2010 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION. |
| | 2010 FBC-B F] 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS NUMBERS OR LETTERS. |
| | |
| | 4) SHEET C4 DRESSING ROOMS DID NOT SHOW A 2010 FL. |
| | ACCESSIBLE DRESSING ROOM LAYOUT AND IN COMPLIANCE WITH; |
| | 4.A)803.2 TURNING SPACE. |
| | TURNING SPACE COMPLYING WITH 304 SHALL BE PROVIDED |
| | WITHIN THE ROOM. |
| | . |
| | 4B) 803.4 BENCHES. A BENCH COMPLYING WITH 903 SHALL BE |
| | PROVIDED WITHIN THE ROOM. |
| | |
| | 4B)(1) 903.1 GENERAL. BENCHES SHALL COMPLY WITH 903. |
| | |
| | 4B)(2) 903.2 CLEAR FLOOR OR GROUND SPACE.CLEAR FLOOR OR |
| | GROUND SPACE COMPLYING WITH 305 SHALL BE PROVIDED AND |
| | SHALL BE POSITIONED AT THE END OF THE BENCH SEAT AND |
| | PARALLEL TO THE SHORT AXIS OF THE BENCH. |
| | |
| | 4B)(3) 903.3 SIZE. BENCHES SHALL HAVE SEATS THAT ARE 42 |
| | INCHES (1065 MM) LONG MINIMUM AND 20 INCHES (510 MM) |
| | DEEP MINIMUM AND 24 INCHES (610 MM) DEEP MAXIMUM. |
| | |
| | 4B)(4) 903.4 BACK SUPPORT. THE BENCH SHALL PROVIDE FOR |
| | BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK |
| | SUPPORT SHALL BE 42 INCHES (1065 MM) LONG MINIMUM AND |
| | SHALL EXTEND FROM A POINT 2 INCHES (51 MM) MAXIMUM |
| | ABOVE THE SEAT SURFACE TO A POINT 18 INCHES (455 MM) |
| | MINIMUM ABOVE THE SEAT SURFACE. BACK SUPPORT SHALL BE |
| | 21/2 INCHES (64 MM) MAXIMUM FROM THE REAR EDGE OF THE |
| | SEAT MEASURED HORIZONTALLY. |
| | |
| | 5) THE PLANS DIDN'T SHOW DETAILS OF THE CASH WRAP AND |
| | COMPLIANCE WTIH 2010 FL ACCESSIBILITY CODE: |
| | 904.4 SALES AND SERVICE COUNTERS. |
| | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| | SERVICE COUNTER TOP. |
| | |
| | EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A |
| | COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A |
| | REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK |
| | STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL |
| | BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION |
| | WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH |
| | 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR |
| | GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF |
| | THE COUNTER. |
| | |
| | 904.4.1 PARALLEL APPROACH. |
| | A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915 |
| | MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| | ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| | FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915 |
| | MM) MINIMUM LENGTH OF COUNTER. |
| | |
| | EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS |
| | THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER |
| | SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE |
| | THE FINISH FLOOR. |
| | |
| | 904.4.2 FORWARD APPROACH. |
| | A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760 |
| | MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| | SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH |
| | 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| | FOR A FORWARD APPROACH TO THE COUNTER. |
| | |
| | 6) PLANS DID NOT PROVIDE DETAILS FOR THE ACCESSIBLE |
| | GRAB BARS REQUIRED IN THE ACCESSIBLE RESTROOMS. 2010 FL |
| | ACCESS : |
| | |
| | 6)(1) 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM) |
| | MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE, |
| | EXCEPT THAT AT WATER CLOSETS FOR CHILDREN?S USE |
| | COMPLYING WITH 604.9, GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION 18 INCHES (455 MM) MINIMUM AND 27 |
| | INCHES (685 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE. THE HEIGHT OF THE |
| | LOWER GRAB BAR ON THE BACK WALL OF A BATHTUB SHALL |
| | COMPLY WITH 607.4.1.1 OR 607.4.2.1. |
| | |
| | 6)(2) 609.7 INSTALLATION. GRAB BARS SHALL BE INSTALLED |
| | IN ANY MANNER THAT PROVIDES A GRIPPING SURFACE AT THE |
| | SPECIFIED LOCATIONS AND THAT DOES NOT OBSTRUCT THE |
| | REQUIRED CLEAR FLOOR SPACE. |
| | |
| | 6)(3) 609.8 STRUCTURAL STRENGTH. ALLOWABLE STRESSES |
| | SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A |
| | VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS (1112 N) IS |
| | APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER, |
| | MOUNTING DEVICE, OR SUPPORTING STRUCTURE. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |