Plan Review Notes
Plan Review Notes For Permit 14040145
Permit Number 14040145
Review Stop P
Sequence Number 1
Notes
Date Text
2014-04-21 06:23:12PLUMBING PLAN REVIEW
 PERMIT: 14040145
 ADD: 701 S ROSEMARY AVE. # 128
 CONT: MASTER PLAN INC
 TEL: (561)683-9972
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 21/2014
 ACTION: DENIED
  
 1) THE PLANS DO NOT PROVIDE THE TENANTCY OCCUPANT LOAD
 OR OCCUPANCY. THE REQUIRED FIXTURE COUNT FOR PLUMBING
 FIXTURES IS NOT PROVIDED ON THE PLANS.
 PLANS DO NOT PROVIDE THE MINIMUM CRITERIA FOR PLAN
 REVIEW. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 PLUMBING PLAN REVIEW
 107.3.5.1.3 MINIMUM PLAN REVIEW CRITERIA FOR PLUMBING.
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
  
  
 2) THE PLANS INDICATE THE TOILET FACILITIES LOCATED
 WITHIN THE STCKROOM AREA. 2010 FBC-PLUMBING:
  
 403.3 REQUIRED PUBLIC TOILET FACILITIES.
 CUSTOMERS, PATRONS AND VISITORS SHALL BE PROVIDED WITH
 PUBLIC TOILET FACILITIES IN STRUCTURES AND TENANT
 SPACES INTENDED FOR PUBLIC UTILIZATION. THE NUMBER OF
 PLUMBING FIXTURES LOCATED WITHIN THE REQUIRED TOILET
 FACILITIES SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 403 FOR ALL USERS. EMPLOYEES SHALL BE PROVIDED WITH
 TOILET FACILITIES IN ALL OCCUPANCIES. EMPLOYEE TOILET
 FACILITIES SHALL BE EITHER SEPARATE OR COMBINED
 EMPLOYEE AND PUBLIC TOILET FACILITIES.
  
 403.3.1 ACCESS.
 THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY
 SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES
 SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR
 OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO
 THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 3) THE PLANS INDICATE A 3 COMPARTMENT SINK AS WELL AS A
 SEPARATE HAND SINK. THESE ARE REQUIREMENTS FROM PUBLIC
 FOOD SERVICE ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS
 DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500
 FLORIDA STATUTES AND CHAPTER 509 FLORIDA STATUTES,
 PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE USE OF
 THIS OCCUPANCY, A GREASE INTERCEPTOR MAY BE REQUIRED.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIED. FBC-P
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved