| 2014-04-21 06:18:41 | BUILDING PLAN REVIEW |
| | PERMIT: 14040145 |
| | ADD: 701 S ROSEMARY AVE. # 128 |
| | CONT: MASTER PLAN INC |
| | TEL: (561)683-9972 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. APRIL 21/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLANS DO NOT PROVIDE THE MINIMUM CRITERIA FOR PLAN |
| | REVIEW. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | BUILDING PLAN REVIEW |
| | PERMIT: 14040145 |
| | |
| | 1) 1) PLANS DO NOT PROVIDE THE MINIMUM CRITERIA FOR |
| | PLAN REVIEW. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | BUILDING PLAN REVIEW |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | MINIMUM BUILDING TYPE |
| | OCCUPANCY TYPE/ ASSUMED MERCANTILE FOR THIS REVIEW |
| | SPRINKLERED/ NOT SPRINKLERED |
| | OCCUPANCY LOAD |
| | MEANS OF EGRESS |
| | |
| | 2) ASSUMED THIS IS A MEERCANTILE OCCUPANCY WITH 30 SQ |
| | FT / OCCUPANT OVER 2100 SQ FT IN THE MERCANTILE AREA |
| | ALONE, OCCUPANT LOAD OVER 50 REQUIRING (2) EXITS, |
| | PLEASE PROVIDE COMPLIANCE WITH: |
| | 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| | THIS SECTION. |
| | 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| | ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE |
| | SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE |
| | ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H |
| | OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS |
| | TRAVEL TO AN EXIT. |
| | EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H, |
| | S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING |
| | ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD |
| | OCCUPANCY GROUP. |
| | |
| | 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| | EXCEPTIONS: |
| | 1. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH A KITCHEN |
| | AREA SERVING ADJOINING ROOMS CONSTITUTING PART OF THE |
| | SAME DWELLING UNIT OR SLEEPING UNIT. |
| | |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| | FOLLOWING ARE MET: |
| | |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |