Plan Review Notes
Plan Review Notes For Permit 14040112
Permit Number 14040112
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-07 13:30:49RESIDENTIAL (R3) REROOF, BUILDING REVIEW COMMENTS.
 CODE; 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY LIMITATION #5.6 OF FLORIDA PRODUCT APPROVAL
 FL2948 SUBMITTED. SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 ***NOTE: THIS PROPERTY IS LOCATED IN EXPOSURE "D".
 DESIGN PROFESSIONAL TO TAKE THIS INTO CONSIDERATION
 WHEN DOING THE RAS 117 CALCULATIONS.
  
 2- THE SELECTED ASSEMBLY "W-1" DOESN'T MEET THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 FOR ROOF ZONE #1. NEED
 TO SELECT ANOTHER ASSEMBLY AS REQUIRED BY LIMITATION
 #5.6 OF FLORIDA PRODUCT APPROVAL SUBMITTED. DESIGN
 PROFESSIONAL DOING THE RAS 117 CALCULATIONS TO
 COORDINATE THE CALCULATIONS WITH NEW SELECTED ASSEMBLY.
  
 3- NEED TO PROVIDE THE LATEST REVISION OF FLORIDA
 PRODUCT APPROVAL FL2948. THE CURRENT FLORIDA PRODUCT
 APPROVAL IS FL2948-R8 NOT FL2948-R7. RESUBMIT CURRENT
 NOA AS REQUIRED BY DCA RULE 9N-3. ***NOTE: DESIGN
 PROFESSIONAL DOING THE RAS 117 CALCULATIONS TO
 COORDINATE WITH NEW FLORIDA PRODUCT APPROVAL.
  
 4- PROVIDE 2 COPIES OF THE CURRENT FLORIDA PRODUCT
 APPROVAL. ONLY ONE COPY WAS SUBMITTED AT THIS TIME.
 SEC. 107.1 CITY AMENDMENTS TO FBC
  
 5- PROVIDE TOTAL SQUARE FOOTAGE OF FLAT ROOF TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE VALUATION OF
 THE PROJECT. SEC. 109.3 CITY AMENDMENTS TO FBC.
  
 6- THE VALUE OF THE HOUSE IS OVER $300,000. NEED TO
 PROVIDE COMPLIANCE WITH THE ROOF TO WALL CONNECTIONS AS
 REQUIRED BY SEC. 611.8 OF 2010 FBC-EXISTING BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712