Plan Review Notes
Plan Review Notes For Permit 14040100
Permit Number 14040100
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-25 11:56:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE DETAILS ON SECTION 1 ARE NOT CONSISTENT WITH UL
 SYSTEM U433. FOR INSTANCE, THE MIN 3" THICK MINERAL
 WOOL IS NOT INCLUDED IN THE WALL SECTION. FBC 703.2.
 PLEASE REVISE.
  
 2. HOW HAS IT BEEN DETERMINED THAT A 1 HOUR SEPARATION
 IS REQUIRED RATHER THAN A 2 HOUR? IF THE BUILDING IS
 FULLY SPRINKLERED, PLEASE NOTE ON THE PLAN. SEE FBC
 508, TABLE 508.4.
  
  
  