| Plan Review Notes For Permit 14040100 |
| Permit Number |
14040100 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-25 11:56:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE DETAILS ON SECTION 1 ARE NOT CONSISTENT WITH UL | | | SYSTEM U433. FOR INSTANCE, THE MIN 3" THICK MINERAL | | | WOOL IS NOT INCLUDED IN THE WALL SECTION. FBC 703.2. | | | PLEASE REVISE. | | | | | | 2. HOW HAS IT BEEN DETERMINED THAT A 1 HOUR SEPARATION | | | IS REQUIRED RATHER THAN A 2 HOUR? IF THE BUILDING IS | | | FULLY SPRINKLERED, PLEASE NOTE ON THE PLAN. SEE FBC | | | 508, TABLE 508.4. | | | | | | | | | |
|