| 2014-04-09 18:09:27 | BUILDING PLAN REVIEW |
| | PERMIT: 14040070 |
| | ADD: 400 N FLAGLER # PHA-5 |
| | CONT: CONKLING & LEWIS CONSTRUCTION |
| | TEL: (561)833-4441 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 09/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A101 PLAN NOTES # 5 PROVIDES A PARTIAL WIND |
| | DESIGN. |
| | MISSING FROM THE DESIGN ARE THE REQUIRED PRESSURES BOTH |
| | POSITIVE AND NEGATIVE. FOR WIND DESIGN ABOVE 60 FEET |
| | FROM GRADE ASCE 7-10 SHOULD BE USED, 2010 FBC-B |
| | 1609.1.1. ARE THE SLIDING GLASS DOORS THAT ARE BEING |
| | MOVED TO THE NEW LOCATION IN A END ZONE OR INTERIOR |
| | ZONE, THIS WILL ALSO AFFECT THE PRESSURES. |
| | |
| | |
| | |
| | 2) PLEASE PROVIDE A RATIONAL ANALYSIS FOR THE FASTENING |
| | OF THE FRAMES INTO THE (MWFRS) STRUCTURAL ELEMENTS, |
| | COLUMNS, BALCONY FLOOR SLAB AND OVERHEAD BALCONY SLAB. |
| | INCLUDE THE TYPE OF ANCHORS, LENGTH, DIAMETER, QUANTITY |
| | & SPACING OF ANCHORS. THE REUSING OF THE EXISTING DOORS |
| | IS SIMILAR O THE REQUIREMENTS FOR CUSTOM DOORS. |
| | 2010 FBC-B 1715.5.3.2 CUSTOM DOORS. CUSTOM (ONE OF A |
| | KIND) EXTERIOR DOOR ASSEMBLIES SHALL BE TESTED BY AN |
| | APPROVED TESTING LABORATORY OR BE ENGINEERED IN |
| | ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICES. |
| | |
| | 3) THE EXISTING SLIDING GLASS DOORS DID HAVE A OVER |
| | HANG, WITH THE NEW PROPOSED LOCATION THEY WILL NEED TO |
| | MEET WATER INFILTRATION REQUIREMENTS FOUND IN 2010 |
| | FBC-B 1715.5.2.1 TESTING AND LABELING. |
| | EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN |
| | APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE |
| | LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF |
| | ONE OF THE FOLLOWING SPECIFICATIONS: |
| | |
| | ANSI/AAMA/NWWDA 101/I.S. 2 OR ANSI/AAMA/ WDMA/101/I.S. |
| | 2/NAFS OR AAMA/WDMA/CSA 101/I.S. 2/A440 OR TAS202 (HVHZ |
| | SHALL COMPLY WITH TAS202 UTILIZING ASTM E 1300-98 OR |
| | ASTM E 1300-04 OR SECTION 2404). |
| | |
| | EXTERIOR WINDOWS AND SLIDING GLASS DOORS SHALL BE |
| | LABELED WITH A PERMANENT LABEL, MARKING, OR ETCHING |
| | PROVIDING TRACEABILITY TO THE MANUFACTURER AND PRODUCT. |
| | THE FOLLOWING SHALL ALSO BE REQUIRED EITHER ON A |
| | PERMANENT LABEL OR ON A TEMPORARY SUPPLEMENTAL LABEL |
| | APPLIED BY THE MANUFACTURER: INFORMATION IDENTIFYING |
| | THE MANUFACTURER, THE PRODUCT MODEL/SERIES NUMBER, |
| | POSITIVE AND NEGATIVE DESIGN PRESSURE RATING, PRODUCT |
| | MAXIMUM SIZE, GLAZING THICKNESS, IMPACT-RESISTANCE |
| | RATING IF APPLICABLE, FLORIDA PRODUCT APPROVAL NUMBER |
| | OR MIAMI-DADE PRODUCT APPROVAL NUMBER, APPLICABLE TEST |
| | STANDARD(S), AND APPROVED PRODUCT CERTIFICATION AGENCY, |
| | TESTING LABORATORY, EVALUATION ENTITY OR MIAMI-DADE |
| | PRODUCT APPROVAL. |
| | |
| | THE LABELS ARE LIMITED TO ONE DESIGN PRESSURE RATING |
| | PER REFERENCE STANDARD. THE TEMPORARY SUPPLEMENTAL |
| | LABEL SHALL REMAIN ON THE WINDOW OR DOOR UNTIL FINAL |
| | APPROVAL BY THE BUILDING OFFICIAL. |
| | EXCEPTIONS: |
| | 1.DOOR ASSEMBLIES INSTALLED IN NONHABITABLE AREAS WHERE |
| | THE DOOR ASSEMBLY AND AREA ARE DESIGNED TO ACCEPT WATER |
| | INFILTRATION NEED NOT BE TESTED FOR WATER INFILTRATION. |
| | 2.DOOR ASSEMBLIES INSTALLED WHERE THE OVERHANG (OH) |
| | RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT BE TESTED FOR |
| | WATER INFILTRATION. THE OVERHANG RATIO SHALL BE |
| | CALCULATED BY THE FOLLOWING EQUATION: |
| | OH RATIO = OH LENGTH/OH HEIGHT |
| | WHERE: |
| | OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN |
| | OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE. |
| | OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM |
| | THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A |
| | DOOR. |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |