| Plan Review Notes For Permit 14040069 |
| Permit Number |
14040069 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-04 10:49:36 | PLAN DENIED | | | 1) PROVIDE DUCT SIZE FOR EXHAUST DUCT | | | AND SUPPLY DUCT ON THE PLAN. PER SECTION | | | 107 FBC 2010 | | | 2) PLAN SHOWS THREE HOODS APPLICATION | | | SHOWS TWO. | | | 3) REFER TO SECTION 506.3.12.1 TERMINATION | | | ABOVE THE ROOF (40 IN) 2010 FBC (M) | | | 4) SEPARATE APPLICATION, PLAN AND PERMIT | | | REQUIRED FOR SUPPRESSION SYSTEM | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|