Plan Review Notes
Plan Review Notes For Permit 14040069
Permit Number 14040069
Review Stop M
Sequence Number 1
Notes
Date Text
2014-04-04 10:49:36PLAN DENIED
 1) PROVIDE DUCT SIZE FOR EXHAUST DUCT
 AND SUPPLY DUCT ON THE PLAN. PER SECTION
 107 FBC 2010
 2) PLAN SHOWS THREE HOODS APPLICATION
 SHOWS TWO.
 3) REFER TO SECTION 506.3.12.1 TERMINATION
 ABOVE THE ROOF (40 IN) 2010 FBC (M)
 4) SEPARATE APPLICATION, PLAN AND PERMIT
 REQUIRED FOR SUPPRESSION SYSTEM
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676