2014-04-01 10:40:20ELECTRICAL DENIED AND PUT IN DENIED UNDER SMALL P
  
 DENIED FOR THE FOLLOWING DEFICIENCIES:
 NO INDICATION ON PLANS PROVIDED OF HOW MAIN HOUSE PANEL
 IS FED. LINE DIAGRAM AND SUPPORTING DOCUMENTATION
 INDICATES A "GUEST HOUSE" ONLY. PLEASE INDICATE IF IT
 IS FED VIA FEED THROUGH LUGS OR FROM A BRANCH BREAKER.
 IF THE HOUSE PANEL IS FED VIA FEED THROUGH LUGS PLEASE
 SHOW EVIDENCE OF EXISTING PANEL HAVING THE CAPACITY OF
 ACCEPTING 200AMP OCP PRE NEC 408.30 AND 408.36 PLEASE
 PROVIDE SITE PLAN OR COPY OF A SURVEY INDICATING
 LOCATION FOR NEW UNDERGROUND SERVICE LATTERAL INCLUDING
 BURIAL DEPTH NEC 300.5, TYPE OF CONDUIT AND USE OF
 CAUTION TAPE. 300.5 (D) (3) AND CALL FOR UNDERGROUND
 INSPECTION. ADDITIONALLY PLEASE PROVIDE ARC FAULT
 CALCULATION PER NEC 110.9 AND INDICATE AIC RATING ON
 NEW SERVICE SWITCHGEAR.
  
 FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN
 REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS
 EXAMINER, PX3421 WITH THE CITY OF WEST PALM BEACH. I
 CAN BE AT 561-805-6717 OR AT [email protected]
  