| Plan Review Notes For Permit 14031166 |
| Permit Number |
14031166 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-01 10:40:20 | ELECTRICAL DENIED AND PUT IN DENIED UNDER SMALL P | | | | | | DENIED FOR THE FOLLOWING DEFICIENCIES: | | | NO INDICATION ON PLANS PROVIDED OF HOW MAIN HOUSE PANEL | | | IS FED. LINE DIAGRAM AND SUPPORTING DOCUMENTATION | | | INDICATES A "GUEST HOUSE" ONLY. PLEASE INDICATE IF IT | | | IS FED VIA FEED THROUGH LUGS OR FROM A BRANCH BREAKER. | | | IF THE HOUSE PANEL IS FED VIA FEED THROUGH LUGS PLEASE | | | SHOW EVIDENCE OF EXISTING PANEL HAVING THE CAPACITY OF | | | ACCEPTING 200AMP OCP PRE NEC 408.30 AND 408.36 PLEASE | | | PROVIDE SITE PLAN OR COPY OF A SURVEY INDICATING | | | LOCATION FOR NEW UNDERGROUND SERVICE LATTERAL INCLUDING | | | BURIAL DEPTH NEC 300.5, TYPE OF CONDUIT AND USE OF | | | CAUTION TAPE. 300.5 (D) (3) AND CALL FOR UNDERGROUND | | | INSPECTION. ADDITIONALLY PLEASE PROVIDE ARC FAULT | | | CALCULATION PER NEC 110.9 AND INDICATE AIC RATING ON | | | NEW SERVICE SWITCHGEAR. | | | | | | FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN | | | REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS | | | EXAMINER, PX3421 WITH THE CITY OF WEST PALM BEACH. I | | | CAN BE AT 561-805-6717 OR AT [email protected] | | | |
|