| Plan Review Notes For Permit 14031153 |
| Permit Number |
14031153 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-05-22 19:21:18 | APPROVED W/THE FOLLOWING NOTES: | | | | | | 1. AS PER NEC THE INTERIOR OF AN UNDERGROUND (OR IN | | | CONCRETE SLAB) RACEWAY SHALL BE CONSIDERED A WET | | | LOCATION; ALL CONDUCTORS WITHIN THE RACEWAY SHALL BE | | | LISTED ACCORDINGLY. | | | | | | 2. HAVC IN ATTIC NOTICE: HVAC EQUIPMENT INSTALLED IN | | | ATTICS ARE SUBJECT TO SPECIFIC NEC REQUIREMENTS: | | | NEC 110.33(B) REQUIRES A PERMANENT LADDER TO THE ATTIC | | | NEC 210.63 REQUIRES A SERVICE OUTLET INSIDE THE ATTIC | | | NEC 210.70 REQUIRES THAT THERE BE A LIGHT INSIDE THE | | | ATTIC & | | | NEC 410.11 REQUIRES THAT THE LIGHT HAVE A GUARD AROUND | | | THE LAMP | | | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|