Plan Review Notes
Plan Review Notes For Permit 14031144
Permit Number 14031144
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-15 14:37:012010 FBC
 907.1.2 FIRE ALARM SHOP DRAWINGS.
 SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHALL BE SUBMITTED
 FOR REVIEW AND APPROVAL PRIOR TO SYSTEM INSTALLATION,
 AND SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL OF THE
 FOLLOWING:
  
 1. A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS.
 2. LOCATIONS OF ALARM-INITIATING DEVICES.
 3. LOCATIONS OF ALARM NOTIFICATION APPLIANCES,
 INCLUDING CANDELA RATINGS FOR VISIBLE ALARM
 NOTIFICATION APPLIANCES.
 4. LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS
 AND NOTIFICATION POWER SUPPLIES.
 5. ANNUNCIATORS.
 6. POWER CONNECTION.
 7. BATTERY CALCULATIONS.
 8. CONDUCTOR TYPE AND SIZES.
 9. VOLTAGE DROP CALCULATIONS.
 10. MANUFACTURERS' DATA SHEETS INDICATING MODEL NUMBERS
 & LISTING INFORMATION FOR EQUIPMENT, DEVICES &
 MATERIALS.
 11. DETAILS OF CEILING HEIGHT AND CONSTRUCTION.
 12. THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS.
 13. CLASSIFICATION OF THE SUPERVISING STATION.
  
 FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN
 REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS
 EXAMINER, PX3421 WITH THE CITY OF WEST PALM BEACH.
 I CAN BE AT 561-805-6717 OR AT [email protected]
  
 PUT PLANS IN SMALL DENIED PLANS DRAWER "A". DAH
  