| Plan Review Notes For Permit 14031144 |
| Permit Number |
14031144 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-15 14:37:01 | 2010 FBC | | | 907.1.2 FIRE ALARM SHOP DRAWINGS. | | | SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHALL BE SUBMITTED | | | FOR REVIEW AND APPROVAL PRIOR TO SYSTEM INSTALLATION, | | | AND SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL OF THE | | | FOLLOWING: | | | | | | 1. A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS. | | | 2. LOCATIONS OF ALARM-INITIATING DEVICES. | | | 3. LOCATIONS OF ALARM NOTIFICATION APPLIANCES, | | | INCLUDING CANDELA RATINGS FOR VISIBLE ALARM | | | NOTIFICATION APPLIANCES. | | | 4. LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS | | | AND NOTIFICATION POWER SUPPLIES. | | | 5. ANNUNCIATORS. | | | 6. POWER CONNECTION. | | | 7. BATTERY CALCULATIONS. | | | 8. CONDUCTOR TYPE AND SIZES. | | | 9. VOLTAGE DROP CALCULATIONS. | | | 10. MANUFACTURERS' DATA SHEETS INDICATING MODEL NUMBERS | | | & LISTING INFORMATION FOR EQUIPMENT, DEVICES & | | | MATERIALS. | | | 11. DETAILS OF CEILING HEIGHT AND CONSTRUCTION. | | | 12. THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. | | | 13. CLASSIFICATION OF THE SUPERVISING STATION. | | | | | | FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN | | | REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS | | | EXAMINER, PX3421 WITH THE CITY OF WEST PALM BEACH. | | | I CAN BE AT 561-805-6717 OR AT [email protected] | | | | | | PUT PLANS IN SMALL DENIED PLANS DRAWER "A". DAH | | | |
|