Plan Review Notes
Plan Review Notes For Permit 14031118
Permit Number 14031118
Review Stop P
Sequence Number 1
Notes
Date Text
2014-06-06 09:54:442010 FBC
  
 DENIED BY PLUMBING
  
 1) THE PLUMBING RISER DIAGRAM ON SHEET M-1 SHOWS A
 HORIZONTAL WASTE ARM FROM THE ISLAND SINK TO THE
 VERTICAL DRAIN FOR THE DOUBLE KITCHEN SINK. TO DO THIS
 THE WASTE ARM WOULD HAVE TO BE ABOVE THE FLOOR OF THE
 KITCHEN. THE ISLAND SINK SHOULD BE VENTED WITH AN AAV (
 AIR ADMITTANCE DEVICE ) AND THE HORIZONTAL BRANCH DRAIN
 SHOULD CONNECT TO THE BUILDING DRAIN AS SHOWN IN THE
 PLUMBING FLOOR PLAN. FBCR P3005.3 AND P3114
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]