Plan Review Notes
Plan Review Notes For Permit 14031118
Permit Number 14031118
Review Stop G
Sequence Number 1
Notes
Date Text
2014-06-06 09:55:562010 FBC
  
 GAS REVIEW IS DENIED
 THERE IS NOT ENOUGH INFORMATION PROVIDED FOR REVIEW.
  
 1) CLEARLY SHOW ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LENGTHS PER FBC 2010 FUEL GAS.
  
 2) SPECIFY THE BTU LOAD OF EACH APPLIANCE AND THE BTU
 LOAD ON THE SYSTEM. REFER TO 2010 FBCR G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU G2413.4 (21)
  
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY ( METER
 ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR
 SYSTEM PER THE 2010 FBCR APPENDIX A - USE OF CAPACITY
 SECTION A.3.1 (4) .
  
 4) INDICATE THE DELIVERY PRESSURE ( PSI ) PER FBCR
 G2413.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 5) SPECIFY THE PIPE SIZING TABLE OR TABLES THAT WAS
 USED TO DESIGN THE SYSTEM. FBCR 402.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714