| Plan Review Notes For Permit 14031118 |
| Permit Number |
14031118 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-06 09:55:56 | 2010 FBC | | | | | | GAS REVIEW IS DENIED | | | THERE IS NOT ENOUGH INFORMATION PROVIDED FOR REVIEW. | | | | | | 1) CLEARLY SHOW ALL CUT SECTIONS OF PIPE AND | | | CORRESPONDING LENGTHS PER FBC 2010 FUEL GAS. | | | | | | 2) SPECIFY THE BTU LOAD OF EACH APPLIANCE AND THE BTU | | | LOAD ON THE SYSTEM. REFER TO 2010 FBCR G2412.8 THRU | | | G2413.6.1 AND TABLES G2413.4(1) THRU G2413.4 (21) | | | | | | 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY ( METER | | | ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR | | | SYSTEM PER THE 2010 FBCR APPENDIX A - USE OF CAPACITY | | | SECTION A.3.1 (4) . | | | | | | 4) INDICATE THE DELIVERY PRESSURE ( PSI ) PER FBCR | | | G2413.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 5) SPECIFY THE PIPE SIZING TABLE OR TABLES THAT WAS | | | USED TO DESIGN THE SYSTEM. FBCR 402.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|