| 2014-04-24 12:54:10 | THE FOLLOWING ITEMS NEED ATTENTION FOR ACCEPTANCE: | | | 1. YOU SHALL PROVIDE A TRUE SERVICE RISER, NOT THIS | | | ILLEGIBLE GENERIC DRAWING. | | | 2. YOU SHALL SUBMIT A PANEL SCHEDULE WITH PROPER | | | NOTATIONS. | | | 3. CARBON MONOXIDE DETECTORS AS PER FBC-R 314 & 315 | | | SHALL BE PROVIDED. | | | 4. THERE ARE TWO (2) CONDENSING UNITS ON THE ELECTRICAL | | | PLANS, BUT THEIR RESPECTIVE AIR HANDLERS ARE NOT | | | INDICATED. | | | 5. THE LOCATION OF THE AIR HANDLERS AND THEIR | | | RESPECTIVE DISCONNECTS SHALL BE INDICATED ON THE | | | ELECTRICAL PLANS. THE MECHANICAL PLANS SHOW WHAT APPEAR | | | TO BE AIR HANDLERS IN THE ATTIC, IF THAT IS THE CASE, | | | ADDITIONAL REQUIREMENTS SHALL APPLY. | | | 6. THE FOUR LIGHTING CIRCUITS FOR THE UNFINISHED ATTIC | | | SHALL BE REFLECTED ON THE DRAWING. | | | 7. AS PER NEC 314.27, THE CEILING BOXES SHALL BE LISTED | | | FOR 50#'S | | | 8. THE ELECTRICAL NOTES AS PRESENTED ON THE PLANS SHALL | | | BE CORRECTED TO MEET NEC 2008 REQUIREMENTS. | | | 9. REVISE THE OUTLET LOCATION TO COMPLY WITH NEC 210.52 | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|