2014-04-24 12:54:10THE FOLLOWING ITEMS NEED ATTENTION FOR ACCEPTANCE:
 1. YOU SHALL PROVIDE A TRUE SERVICE RISER, NOT THIS
 ILLEGIBLE GENERIC DRAWING.
 2. YOU SHALL SUBMIT A PANEL SCHEDULE WITH PROPER
 NOTATIONS.
 3. CARBON MONOXIDE DETECTORS AS PER FBC-R 314 & 315
 SHALL BE PROVIDED.
 4. THERE ARE TWO (2) CONDENSING UNITS ON THE ELECTRICAL
 PLANS, BUT THEIR RESPECTIVE AIR HANDLERS ARE NOT
 INDICATED.
 5. THE LOCATION OF THE AIR HANDLERS AND THEIR
 RESPECTIVE DISCONNECTS SHALL BE INDICATED ON THE
 ELECTRICAL PLANS. THE MECHANICAL PLANS SHOW WHAT APPEAR
 TO BE AIR HANDLERS IN THE ATTIC, IF THAT IS THE CASE,
 ADDITIONAL REQUIREMENTS SHALL APPLY.
 6. THE FOUR LIGHTING CIRCUITS FOR THE UNFINISHED ATTIC
 SHALL BE REFLECTED ON THE DRAWING.
 7. AS PER NEC 314.27, THE CEILING BOXES SHALL BE LISTED
 FOR 50#'S
 8. THE ELECTRICAL NOTES AS PRESENTED ON THE PLANS SHALL
 BE CORRECTED TO MEET NEC 2008 REQUIREMENTS.
 9. REVISE THE OUTLET LOCATION TO COMPLY WITH NEC 210.52
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  