| 2014-06-03 11:32:14 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ARCHITECT SHOWN ON THE TITLE BLOCK NEEDS TO SIGN AND |
| | SEAL ALL DRAWINGS, NOT JUST THE COVER PAGE, AS REQUIRED |
| | BY SEC. 61G1-16 OF FLORIDA ADMINISTRATIVE CODE AND |
| | CHAPTER 481 FLORIDA STATUTE. |
| | |
| | 2- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3 OF |
| | 2010 FBC-RESIDENTIAL. |
| | ***NOTE: SITE PLAN ON COVER SHEET SHOWS DRAINAGE ARROWS |
| | LEADING THE WATER TO THE BACK OF THE HOUSE. THIS IS |
| | GOING TO CREATE DRAINAGE PROBLEMS. AND WATER CAN'T BE |
| | DIVERTED TO THE NEIGHBORS. REVISE AS REQUIRED. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| | PROFIT AND DESIGN PROFESSIONAL FEES. VALUATION WAS |
| | UPDATED TO $169,730. THE PERMIT FEE BALANCE IS |
| | $3998.40. |
| | |
| | 4- SHEET A-1: |
| | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE FIREPLACE. AS REQUIRED BY CHAPTER |
| | 10 OF THE 2010 FBC-RESIDENTIAL. AND, PROVIDE |
| | MANUFACTURER'S SPECIFICATIONS AND DETAILS FOR DIRECT |
| | VENT GAS LOG FIREPLACE SHOWN ON PLANS. |
| | |
| | B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL |
| | THE STAIRS, HANDRAILS, GUARDRAILS INTERIOR STAIRWAY |
| | LEADING TO SECOND FLOOR AND FRONT AND REAR PORCHES. |
| | REQUIRED BY SEC. R311.7, SEC. R312 AND BY TABLE R301.5 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) PROVIDE COMPLETE DETAILS/ SECTIONS AND |
| | SPECIFICATIONS FOR THE CONSTRUCTION OF THE STAIRWAY. |
| | SEC. R301. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) METAL ROOF PANELS. NOA 10-1214.12 SUBMITTED IS FOR |
| | STEEL DECKS. NEED NOA FOR WOOD DECK AS SHOWN ON PLANS. |
| | |
| | B) CASEMENT WINDOWS AS SPECIFIED ON WINDOW SCHEDULE. ( |
| | NOA 11-1013.14 SUBMITTED IS FOR SINGLE HUNG WINDOWS). |
| | |
| | C) ALL FIXED WINDOWS AS SHOWN ON WINDOW SCHEDULE AND |
| | EXTERIOR ELEVATIONS. |
| | |
| | D) ROOF RIDGE VENT AS SHOWN ON ROOF PLAN. |
| | |
| | E) PRECAST LINTELS IF SPECIFIED ON PLANS. COORDINATE |
| | WITH ITEM # 7(C) BELOW. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 7- SHEET S-1: |
| | A) STRUCTURAL PLANS TO PROVIDE ALL THE DESIGN CRITERIA: |
| | SPECIFY ALL DEAD AND LIVE LOADS, INCLUDING THE ATTIC |
| | LIVE LOADS AS REQUIRED BY TABLE R301.5 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | B) PROVIDE COMPLETE ROOF FRAMING PLAN SPECIFYING ALL |
| | STRUCTURAL CONNECTORS FOR ALL ROOF TRUSSES, ALL PORCH |
| | BEAMS, ALL CONVENTIONAL FRAMING MEMBERS TO VERIFY |
| | COMPLIANCE WITH SEC. R801.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) PROVIDE COMPLETE FRAMING PLAN SHOWING ALL COLUMNS, |
| | BEAMS, LINTELS IN MASONRY CONSTRUCTION, HEADERS IN |
| | FRAMED WALLS, ETC. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | D) SPECIFY ROOF SHEATHING NAILING ZONES AS REQUIRED BY |
| | FIGURE R803.2.3.1 (ALL GABLE ENDS 5'-0" MIN. ARE ROOF |
| | ZONE #3). AND, SEC. R803.2.3.1 REQUIRES 8D RING SHANK |
| | NAILS MIN. |
| | |
| | 8- REVISE SPECIFICATIONS ON ALL WALL SECTIONS ON SHEET |
| | S-2. MASONRY VERTICAL REINFORCEMENT IS NOT @ 96" O.C. |
| | SEE CMU CONSTRUCTION SPECIFICATIONS ON ENGINEERING |
| | ANALYSIS BY ENGINEER D. JEFFREY BAIR AND REVISE ALL |
| | DRAWINGS AS REQUIRED. SEC. R301. |
| | |
| | 9- PROVIDE 2 COPIES OF THE SOIL TEST REPORT. ONLY ONE |
| | COPY WAS SUBMITTED. SEC. 107.1 CITY AMENDMENTS. |
| | |
| | 10- SHEET S-2: |
| | A) ENGINEERING WIND ANALYSIS DONE BY D. JEFFREY BAIR: |
| | REVISE THE ROOF SHEATHING NAILING SPECIFICATIONS. NEED |
| | TO SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC. |
| | R803.2.3.1 OF 2010 FBC-RESIDENTIAL. ALSO, REVISE ROOF |
| | SHEATHING SPECIFICATIONS ON ALL WALLS SECTIONS ON SHEET |
| | S-2 AS REQUIRED. |
| | |
| | B) COORDINATE ALL DETAILS AND SPECIFICATIONS WITH THE |
| | ENGINEER WIND ANALYSIS REPORT SUBMITTED. SEC. R301. |
| | |
| | C) ACCORDING TO THE SOIL TEST REPORT SUBMITTED, THE |
| | BOTTOM OF THE FOOTING SHALL BE PLACED A MINIMUM OF 18 |
| | INCHES BELOW THE LOWEST ADJACENT GRADE. PLANS AND |
| | SECTIONS DON'T MAKE ANY REFERENCE TO THIS REQUIREMENT. |
| | REVISE PLANS AS REQUIRED TO INCLUDE THIS INFORMATION. |
| | OR PROVIDE ENGINEERING ANALYSIS SHOWING WHY IS NOT |
| | REQUIRED. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF ALL THE GABLE ENDS SHOWN ON PLANS TO |
| | VERIFY COMPLIANCE WITH SEC. R609.4 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 12 - PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | THE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS SHOWING |
| | COMPLIANCE WITH SEC. R612.10.2. |
| | ***NOTE: BUCKS NEED TO PROVIDE COMPLETE DOOR AND WINDOW |
| | FRAME SUPPORT. SEE SEC. R612.10.2. |
| | |
| | 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | DOORS AND WINDOWS MULLIONS SHOWN ON PLANS AND EXTERIOR |
| | ELEVATIONS TO DEMONSTRATE COMPLIANCE WITH SEC. R612.11. |
| | |
| | 14- PROVIDE EVALUATION REPORT (2 COPIES) FOR THE |
| | ICYNENE INSULATION SPECIFIED ON PLANS TO VERIFY |
| | COMPLIANCE WITH SEC. R316 AND R VALUES REQUIRED ON THE |
| | ENERGY CALCULATIONS. |
| | |
| | 15- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC. |
| | R315. |
| | |
| | 16- REVISE ENERGY CALCULATIONS SUBMITTED (SEC. 103.2.2 |
| | OF 2010 FBC-ENERGY CONSERVATION): |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE |
| | HIS INFORMATION (NAME, LICENSE, ETC.) AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS |
| | FOR PUBLIC RECORDS. |
| | |
| | C) PROVIDE DOOR AND WINDOW SPECS SHOWING THE U-FACTOR |
| | AND SHGC FACTOR SHOWN ON ITEM #7 AS REQUIRED BY SEC. |
| | 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | D) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH AND |
| | AREA WEIGHTED AVERAGE SHGC SHOWN ON ITEM #7. THE |
| | WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE 5 OF 7 |
| | DON'T MATCH PLANS. REVISE AS REQUIRED TO MATCH . |
| | |
| | E) THERE ARE NO 6 BEDROOMS IN THIS HOUSE. ONLY ONE. SEE |
| | PLANS. (AND A FUTURE ONE IN THE ATTIC). |
| | |
| | F) COMPLETE ALL THE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER'S AND BUILDER'S NAME, JURISDICTION |
| | NUMBER, ETC. |
| | |
| | G) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW OBTAINING R19 INSULATION IN THE CONCRETE BLOCK WALL |
| | AS SHOWN ON ITEM #9. |
| | |
| | H) PROVIDE DETAILS AND SPECS SHOWING HOW OBTAINING R30 |
| | INSULATION WITH ICYNENE IN THE CEILING. SEE ICYNENE |
| | EVALUATION REPORT FOR REQUIRED THICKNESS. |
| | |
| | I) PROVIDE PLANS SHOWING THE CEILING FANS SIZES AND |
| | LOCATION TO VERIFY COMPLIANCE WITH THE CEILING FAN |
| | CREDIT AS TAKEN IN ITEM #15. |
| | |
| | J) REVISE THE SPACES ON PAGE 2 OF 7 TO MATCH ACTUAL |
| | SPACES SHOWN ON PLANS. |
| | |
| | K) REVISE WINDOWS (AND DOORS) FRAME ON PAGE 5 OF 7. |
| | THEY ARE ALUMINUM NOT WOOD. SEE PRODUCT APPROVALS AND |
| | REVISE AS REQUIRED. |
| | |
| | 17- A) WINDOW SCHEDULE ON SHEET A-1 CALLS FOR CASEMENT |
| | WINDOWS, WHILE PRODUCT APPROVAL SUBMITTED IS FOR SINGLE |
| | HUNG WINDOWS. CLARIFY/REVISE AS REQUIRED TO MATCH. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | ( ***NOTE: WINDOWS SHOWN ON THE EXTERIOR ELEVATION ON |
| | SHEET A-2 TO MATCH TYPE OF WINDOW SPECIFIED ON THE |
| | WINDOW SCHEDULE. REVISE AS REQUIRED). |
| | |
| | B) FUTURE ATTIC LIVABLE AREA. CLEARLY IDENTIFY TYPE AND |
| | SIZE OF WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310. COORDINATE WITH ITEM 17(A) |
| | ABOVE. OR, CLEARLY SPECIFY ON PLANS THAT ATTIC SPACE |
| | CAN'T NOT BE USED FOR ANY SLEEPING PURPOSE. |
| | |
| | 18- TRUSS PACKAGE SUBMITTED TO COMPLY WITH SEC. |
| | 61G15-31.003 OF FLORIDA ADMINISTRATIVE CODE: |
| | A) NEED TRUSS LAYOUT TO BE SIGNED AND SEALED. (AND, |
| | PROVIDE COMPLETE ENGINEER'S INFORMATION). |
| | |
| | B) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE ON THE |
| | INDEX SHEET. NO COPIES ALLOWED. (CHAPTER 471 FLORIDA |
| | STATUTE). |
| | |
| | C) NEED TO PROVIDE ALL THE INFORMATION OF THE ENGINEER |
| | OF RECORD FOR THIS PROJECT. |
| | |
| | D) NEED THE ENGINEER'S OF RECORD APPROVAL OF THE TRUSS |
| | PACKAGE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |