| 2014-04-16 08:50:09 | 907.1.2 FIRE ALARM SHOP DRAWINGS. [F] | | | | | | SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHALL BE SUBMITTED | | | FOR REVIEW AND APPROVAL PRIOR TO SYSTEM INSTALLATION, | | | AND SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL OF THE | | | FOLLOWING: | | | 1. A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS. | | | 2. LOCATIONS OF ALARM-INITIATING DEVICES. | | | 3. LOCATIONS OF ALARM NOTIFICATION APPLIANCES, | | | INCLUDING CANDELA RATINGS FOR VISIBLE ALARM | | | NOTIFICATION APPLIANCES. | | | 4. LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS | | | AND NOTIFICATION POWER SUPPLIES. | | | 5. ANNUNCIATORS. | | | 6. POWER CONNECTION. | | | 7. BATTERY CALCULATIONS. | | | 8. CONDUCTOR TYPE AND SIZES. | | | 9. VOLTAGE DROP CALCULATIONS. | | | 10. MANUFACTURERS' DATA SHEETS INDICATING MODEL NUMBERS | | | AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND | | | MATERIALS. | | | 11. DETAILS OF CEILING HEIGHT AND CONSTRUCTION. | | | 12. THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. | | | 13. CLASSIFICATION OF THE SUPERVISING STATION. | | | | | | DAVID A. HAYES, ELECTRICAL PLANS EXAMINER. | | | [email protected] 561-508-6717 |
|