| Plan Review Notes For Permit 14031109 |
| Permit Number |
14031109 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-31 14:51:19 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVAL FOR THE CERTAIN-TEED MODIFIED | | | BITUMEN ROOFING HAS A DESIGN PRESSURE OF 60 PSF, WHICH | | | IS TOO LOW FOR THE CORNER AND PERIMETER AREAS. SUBMIT 2 | | | SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING AS REQUIRED BY LIMITATION #7 OF NOA | | | NO.13-0204.03. | | | | | | 2) THE PRODUCT APPROVAL FOR THE OWENS CORNING ROOF | | | VENT, FL# 16828, HAS NOT BEEN APPROVED BY THE STATE AT | | | THIS TIME. IT'S STATUS IS LISTED AS PENDING. PLEASE | | | SUBMIT A CURRENT PRODUCT APPROVAL AS REQUIRED BY DCA | | | RULE 9N-3. | | | | | | 3) ONLY THE COVERSHEET WAS SUBMITTED FOR THE IKO | | | ASPHALT SHINGLES WITH FL# 7006. SUBMIT TWO COPIES OF | | | THE INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE | | | 9N-3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|