2014-04-17 14:58:381865 PALM BEACH LAKES BOULEVARD - SUITE B12
 PERMIT #14031097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A SUITE NUMBER ON THE PLANS.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING DESIGNATED EXITS,
 EXIT PATHS, TRAVEL DISTANCES, COMMON PATH OF TRAVEL
 ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PER NFPA 101 SECTION 7.2.1.5.9, THE LOCK/LATCH
 RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR
 WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE.
  
 MAIN ENTRANCE DOORS WITH KEYED LOCK OR THUMB-TURN LOCK
 TO BE EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 PROVIDE DRAWING NOTE INDICATING AN APPROVED WRITTEN
 EMERGENCY PLAN FOR THE EMERGENCY EGRESS OF OCCUPANTS IS
 REQUIRED PRIOR TO OCCUPANCY. ALL EMPLOYEES SHALL BE
 INSTRUCTED AND PERIODICALLY DRILLED WITH RESPECT TO
 THEIR DUTIES UNDER THE PLAN.
  
 PROVIDE A DRAWING NOTE INDICATING EMPLOYEES SHALL BE
 PERIODICALLY TRAINED OR INSTRUCTED IN THE USE OF
 PORTABLE FIRE EXTINGUISHERS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS OR SUITE NUMBER VISIBLE FROM THE STREET OR
 PARKING LOT. NUMBERS SHALL BE ATTACHED TO THE BUILDING
 AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE
 AND SHALL CONTRAST THE BACKGROUND.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE