| Plan Review Notes For Permit 14031088 |
| Permit Number |
14031088 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-27 18:05:10 | 2010 FBC | | | | | | DENIED | | | | | | 1) SPECIFY THE TYPE OF PIPING MATERIAL BEING USED. | | | | | | 2) INDICATE THE DELIVERY PRESSURE. IF NATURAL GAS | | | SPECIFY .5 PSI OR 2 PSI. FBCR G2413.2 | | | | | | 3) SPECIFY THE TOTAL LOAD ON THE SYSTEM AND THE | | | DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET IN | | | THE SYSTEM. FBCR APPENDIX A SECTION A.3.1(4) | | | | | | 4) SPECIFY THE LOCATION OF THE NEW TANKLESS WATER | | | HEATER AND SHOW THAT IT'S LOCATION COMPLIES WITH THE | | | MANUFACTURER'S REQUIRED CLEARANCES FROM OPENINGS AND | | | COMBUSTIBLES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|